YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
45
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E5-04
(032C)
PM Motor Pole Count
Sets the number of PM motor poles.
Note:
When
A1-02 = 5 or 8 [OLV/PM or EZOLV]
, the maximum value is 48.
4
(2 - 120)
E5-05
(032D)
PM Motor Resistance
(ohms/phase)
Sets the resistance per phase of a PM motor. Set 50% of the line-to-line resistance.
0.100 Ω
(0.000 - 65.000 Ω)
E5-06
(032E)
PM d-axis Inductance
(mH/phase)
Sets the PM motor d-axis inductance.
1.00 mH
(0.00 - 300.00 mH)
E5-07
(032F)
PM q-axis Inductance
(mH/phase)
Sets the PM motor q-axis inductance.
1.00 mH
(0.00 - 600.00 mH)
E5-09
(0331)
PM Back-EMF Vpeak
(mV/(rad/s))
Sets the peak value of PM motor induced voltage.
0.0 mV/(rad/sec)
(0.0 - 2000.0 mV/(rad/s))
E5-24
(0353)
PM Back-EMF L-L Vrms
(mV/rpm)
Sets the RMS value for PM motor line voltage.
0.1 mV/min
-1
(0.0 - 6500.0 mV/min
-1
)
◆
E9: Motor Setting
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E9-01
(11E4)
Motor Type Selection
Sets the type of motor.
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
0
(0 to 2)
E9-02
(11E5)
Maximum Speed
Sets the maximum speed of the motor.
Determined by E9-01
(40.0 - 120.0 Hz)
E9-03
(11E6)
Rated Speed
Sets the rated rotation speed of the motor.
Determined by E9-01
(100 - 7200 min
-1
)
E9-04
(11E7)
Base Frequency
Sets the rated frequency of the motor.
Determined by E9-01
(40.0 - 120.0 Hz)
E9-05
(11E8)
Base Voltage
Sets the rated voltage of the motor.
208 V Class: 230.0 V,
480 V Class: 460.0 V
(208 V Class: 0.0 - 255.0
V,
480 V Class: 0.0 - 510.0
V)
E9-06
(11E9)
Motor Rated Current
(FLA)
Sets the motor rated current in amps.
Determined by E9-01 and
o2-04
(10% to 200% of the
drive rated current)
E9-07
(11EA)
Motor Rated Power
Sets the motor rated output in the units from
o1-58 [Motor Power Unit Selection]
.
Determined by E9-02 and
o2-04
(0.00 - 650.00 kW)
E9-08
(11EB)
Motor Pole Count
Sets the number of motor poles.
4
(2 to 120)
E9-09
(11EC)
Motor Rated Slip
Sets the motor rated slip.
0.000 Hz
(0.000 - 20.000 Hz)
E9-10
(11ED)
Motor Line-to-Line
Resistance
Sets the line-to-line resistance for the motor stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...