464
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
■
T2-12: PM Motor q-Axis Inductance
No.
(Hex.)
Name
Description
Default
(Range)
T2-12
(0736)
PM Motor q-Axis
Inductance
Sets the q-Axis inductance of the motor on a per phase basis.
Determined by T2-02
(0.00 - 600.00 mH)
■
T2-13: Back-EMF Units Selection
No.
(Hex.)
Name
Description
Default
(Range)
T2-13
(0755)
Back-EMF Units Selection
Sets the units that the drive uses to set the induced voltage constant.
0
(0, 1)
0 : mV/(rev/min)
1 : mV/(rad/s)
Note:
•
When
T2-13 = 0
, the drive will use
E5-24 [PM Back-EMF L-L Vrms (mV/rpm)]
and will automatically set
E5-09 [PM Back-EMF Vpeak
(mV/(rad/s))] = 0.0
.
•
When
T2-13 = 1
, the drive will use
E5-09
and will automatically set
E5-24 = 0.0
.
■
T2-14: Back-EMF Voltage Constant (Ke)
No.
(Hex.)
Name
Description
Default
(Range)
T2-14
(0737)
Back-EMF Voltage Constant
(Ke)
Sets the motor induced voltage constant (Ke).
Determined by T2-13
(0.0 - 2000.0)
■
T2-15: Pull-In Current Level
No.
(Hex.)
Name
Description
Default
(Range)
T2-15
(0756)
Pull-In Current Level
Sets the level of the pull-in current as a percentage of
E5-03 [PM Motor Rated Current (FLA)]
.
Usually it is not necessary to change this setting.
30%
(0 - 120%)
If the load inertia is high, increase the setting value.
◆
T4: EZ Tuning
Use
T4 parameters
to input the data necessary for motor parameter Auto-Tuning when
A1-02 = 8 [Control Method
Selection = EZ Vector Control]
. These two modes are available:
T4-01 Setting
Operational overview
Items input for tuning
Items tuned
0
Follow the instructions in the setup wizard on the keypad to
manually enter the necessary motor parameters.
•
T4-02 [Motor Type Selection]
•
T4-03 [Motor Max Revolutions]
•
T4-04 [Motor Rated Revolutions]
•
T4-05 [Motor Rated Frequency]
•
T4-06 [Motor Rated Voltage]
•
T4-07 [Motor Rated Current]
•
T4-08 [Motor Rated Capacity]
•
T4-09 [Number of Poles]
•
E9-01 [Motor Type Selection]
•
E9-02 [Maximum Speed]
•
E9-03 [Rated Speed]
•
E9-04 [Base Frequency]
•
E9-05 [Base Voltage]
•
E9-06 [Motor Rated Current (FLA)]
•
E9-07 [Motor Rated Power]
•
E9-08 [Motor Pole Count]
•
E9-09 [Motor Rated Slip]
•
E9-10 [Motor Line-to-Line Resistance]
1
Do only line-to-line resistance tuning.
Motor Rated Current
E9-10 [Motor Line-to-Line Resistance]
*1
When you use a PM motor or a synchronous reluctance motor, it is not necessary to enter the rated frequency. The drive will use the rated
rotation speed and number of motor poles to automatically calculate the rated frequency.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...