YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
241
Figure 2.40 Jump Frequency
Note:
•
When you set Jump Frequencies 1 to 3, make sure that the parameters do not overlap.
•
When the drive is in the range of the Jump frequency, the frequency reference changes automatically. When Jump is executed, the output
frequency changes smoothly as specified by the values set in
C1-01 [Acceleration Time 1]
and
C1-02 [Deceleration Time 1]
.
■
d3-01: Jump Frequency 1
No.
(Hex.)
Name
Description
Default
(Range)
d3-01
(0294)
Jump Frequency 1
Sets the median value of the frequency band that the drive will avoid.
0.0 Hz
(0.0 - 400.0 Hz)
Note:
Set this parameter to 0.0 Hz to disable the Jump frequency.
■
d3-02: Jump Frequency 2
No.
(Hex.)
Name
Description
Default
(Range)
d3-02
(0295)
Jump Frequency 2
Sets the median value of the frequency band that the drive will avoid.
0.0 Hz
(0.0 - 400.0 Hz)
Note:
Set this parameter to 0.0 Hz to disable the Jump frequency.
■
d3-03: Jump Frequency 3
No.
(Hex.)
Name
Description
Default
(Range)
d3-03
(0296)
Jump Frequency 3
Sets the median value of the frequency band that the drive will avoid.
0.0 Hz
(0.0 - 400.0 Hz)
Note:
Set this parameter to 0.0 Hz to disable the Jump frequency.
■
d3-04: Jump Frequency Width
No.
(Hex.)
Name
Description
Default
(Range)
d3-04
(0297)
Jump Frequency Width
Sets the width of the frequency band that the drive will avoid.
1.0 Hz
(Determined by A1-02)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...