44
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E3-08
(031E)
Motor 2 Mid Point A
Voltage
Sets a middle output voltage for the motor 2 V/f pattern.
Determined by E3-01
(208 V Class: 0.0 - 255.0
V,
480 V Class: 0.0 - 510.0
V)
E3-09
(031F)
Motor 2 Minimum
Output Frequency
Sets the minimum output frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
E3-10
(0320)
Motor 2 Minimum
Output Voltage
Sets the minimum output voltage for the motor 2 V/f pattern.
Determined by E3-01
(208 V Class: 0.0 - 255.0
V,
480 V Class
E3-11
(0345)
Expert
Motor 2 Mid Point B
Frequency
Sets a middle output frequency for the motor 2 V/f pattern. Set this parameter to adjust the
V/f pattern for the constant output range. Usually it is not necessary to change this
parameter.
0.0 Hz
(0.0 - E3-04)
E3-12
(0346)
Expert
Motor 2 Mid Point B
Voltage
Sets a middle output voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/
f pattern for the constant output range. Usually it is not necessary to change this parameter.
0.0 V
(208 V Class: 0.0 - 255.0
V,
480 V Class: 0.0 - 510.0
V)
E3-13
(0347)
Expert
Motor 2 Base Voltage
Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f
pattern for the constant output range. Usually it is not necessary to change this parameter.
0.0 V
(208 V Class: 0.0 - 255.0
V,
480 V Class: 0.0 - 510.0
V)
◆
E4: Motor 2 Parameters
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E4-01
(0321)
Motor 2 Rated Current
Sets the motor rated current for motor 2 in amps.
Determined by o2-04
(10% to 200% of the
drive rated current)
E4-02
(0322)
Motor 2 Rated Slip
Sets the motor rated slip for motor 2.
Determined by o2-04
(0.000 - 20.000 Hz)
E4-03
(0323)
Motor 2 Rated No-Load
Current
Sets the no-load current for motor 2 in amps when operating at the rated frequency and the
no-load voltage.
Determined by o2-04
(Less than 0 - E4-01)
E4-04
(0324)
Motor 2 Motor Poles
Sets the number of poles for motor 2.
4
(2 - 120)
E4-05
(0325)
Motor 2 Line-to-Line
Resistance
Sets the line-to-line resistance for the motor 2 stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
E4-06
(0326)
Motor 2 Leakage
Inductance
Sets the voltage drop from motor 2 leakage inductance as a percentage of Motor Rated
Voltage when motor 2 operates at the rated frequency and rated current.
Determined by o2-04
(0.0 - 60.0%)
E4-10
(0340)
Motor 2 Iron Loss
Sets the motor iron loss for motor 2.
Determined by o2-04
(0 - 65535 W)
E4-11
(0327)
Motor 2 Rated Power
Sets the motor rated power in the units from
o1-58 [Motor Power Unit Selection]
.
Determined by o2-04
(0.00 - 650.00 HP)
◆
E5: PM Motor Settings
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E5-01
(0329)
PM Motor Code Selection
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to
automatically set some parameters to their correct settings.
FFFF
(0000 - FFFF)
E5-02
(032A)
PM Motor Rated Power
Sets the PM motor rated output in the units set in
o1-58 [Motor Power Unit Selection]
.
Determined by o2-04
(0.13 - 650.00 HP)
E5-03
(032B)
PM Motor Rated Current
(FLA)
Sets the PM motor rated current (FLA).
Determined by o2-04
(10% to 200% of the
drive rated current)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...