d7: Offset Frequency
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
d7-01
(02B2)
RUN
Offset Frequency 1
Uses
H1-xx = 44 [MFDI Function Select = Add Offset Frequency 1 (d7-01)]
as a
percentage of the Maximum Output Frequency to add or subtract the set frequency to/from
the frequency reference.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the maximum
output frequency.
•
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
•
A1-02 = 8
:
E9-02 [Maximum Speed]
0.0%
(-100.0 - +100.0%)
d7-02
(02B3)
RUN
Offset Frequency 2
Uses
H1-xx = 45 [MFDI Function Select = Add Offset Frequency 2 (d7-02)]
as a
percentage of the Maximum Output Frequency to add or subtract the set frequency to/from
the frequency reference.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the maximum
output frequency.
•
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
•
A1-02 = 8
:
E9-02 [Maximum Speed]
0.0%
(-100.0 - +100.0%)
d7-03
(02B4)
RUN
Offset Frequency 3
Uses
H1-xx = 46 [MFDI Function Select = Add Offset Frequency 3 (d7-03)]
as a
percentage of the Maximum Output Frequency to add or subtract the set frequency to/from
the frequency reference.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the maximum
output frequency.
•
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
•
A1-02 = 8
:
E9-02 [Maximum Speed]
0.0%
(-100.0 - +100.0%)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...