359
Output frequency reduction = Motor rated slip before KEB operation × (
L2-08
/100) × 2
■
L2-09: KEB Minimum Frequency Level
No.
(Hex.)
Name
Description
Default
(Range)
L2-09
(048D)
Expert
KEB Minimum Frequency
Level
Sets the quantity of output frequency reduction used as a percentage of
E2-02 [Motor Rated Slip]
when KEB operation starts.
20%
(0 - 100%)
These conditions set the quantity of decrease:
•
Motor rated slip × (
L2-09
/100)
•
The larger value between the value calculated with
L2-08
and the value calculated with
L2-09
■
L2-10: Minimum KEB Time
No.
(Hex.)
Name
Description
Default
(Range)
L2-10
(048E)
Expert
Minimum KEB Time
Sets the minimum length of time to operate the KEB after the drive detects a momentary power loss.
50 ms
(0 - 25500 ms)
When you return power while KEB is operating, the drive continues KEB operation until the time set in
L2-10
is
expired. When you input
KEB Ride-Thru 1/2 [H1-xx = 65, 66, 7A, or 7B]
into the drive and the DC bus voltage is less
than
L2-05 [Undervoltage Detect Level (Uv1)]
, KEB operation continues until the time set in
L2-10
is expired.
When you input KEB Ride-Thru, KEB operation continues after the time set in
L2-10
is expired. When you cancel
KEB Ride-Thru, the motor accelerates again. When you do not input KEB Ride-Thru during the time set in
L2-10
, the
drive accelerates to the frequency reference that the drive had before power loss in the applicable acceleration time.
Note:
•
When
L2-01 = 0, 1, or 2 [Disabled, Enabled, or Enabled when CPU is Running]
, increase the value of
L2-10
. Set
L2-10
to cancel KEB
operation if the KEB Ride-Thru is not input
•
Set this parameter to 0 to disable the function.
■
L2-11: KEB DC Bus Voltage Setpoint
No.
(Hex.)
Name
Description
Default
(Range)
L2-11
(0461)
Expert
KEB DC Bus Voltage
Setpoint
Sets the target value that controls the DC bus voltage to a constant level in Single Drive KEB Ride-
Thru 2. Sets the DC bus voltage level that completes the KEB operation for all other KEB methods.
Determined by E1-01
(Determined by E1-01)
■
L2-29: Kinetic Energy Backup Method
No.
(Hex.)
Name
Description
Default
(Range)
L2-29
(0475)
Expert
Kinetic Energy Backup
Method
Sets the KEB function operation mode.
0
(0 - 1)
0 : Single Drive KEB Ride-Thru 1
The drive monitors the DC bus voltage and uses regenerative energy from the motor to hold the DC bus voltage at the
level set in
L2-11 [KEB DC Bus Voltage Setpoint]
.
The KEB operation continues and the deceleration rate changes as specified by
C1-09 [Fast Stop Time]
.
Note:
•
If the drive detects
Uv1 [DC Bus Undervoltage]
during KEB operation, decrease the value of
C1-09
.
•
If the drive detects
ov [Overvoltage]
during KEB operation, increase the value of
C1-09
.
1 : Single Drive KEB Ride-Thru 2
The drive does KEB operation and automatically calculates the deceleration rate to make sure that the main circuit
electrical energy and main current voltage from motor regenerative energy is equal to
L2-11
.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...