TOEPYAIHV6002A HV600 Drive Programming
Setting Value
Function
Description
Ref.
9F
DWEZ Disable
Sets operation of the DriveWorksEZ program saved in the drive.
ON : Disable
OFF : Enabled
Note:
Set
A1-07 = 2 [DriveWorksEZ Function Selection = Digital input]
to use this function.
A8
PI2 Control Disable
Sets the command to disable the PI2 Control function. Parameter
S3-12 [PI2 Control Disable Mode Sel]
sets the
output performance.
ON : Enabled
OFF : Disabled
AA
PI2 Control Inverse
Operation
Sets the command to change the sign of the PI2 Control input.
AB
PI2 Control Integral Reset
Sets the command to reset the PI2 Control integral value.
Note:
This input has priority over
H1-xx = AC [MFDI Function Selection = PI2 Control Integral Hold]
.
AC
PI2 Control Integral Hold
Sets the command to lock the PI2 Control integral value.
AD
Select PI2 Control PI
Parameters
Sets the command to use the
S3-06 [PI2 Control Proportional Gain]
and
S3-07 [PI2 Control Integral Time]
values
instead of the
b5-02 [Proportional Gain (P)]
and
b5-03 [Integral Time (I)]
values. Set
S3-01 = 0 [PI2 Control Enable
Selection = Disabled]
to enable this function.
Note:
This multi-function input does not have an effect on PI2 Control. Use this input for the primary PI controller (
b5-
xx
).
AF
Emergency Override
FWD
Sets the command to use the speed set in
S6-02 [Emergency Override Ref Selection]
to run the drive in the forward
direction.
B0
Emergency Override
REV
Sets the command to use the speed set in
S6-02 [Emergency Override Ref Selection]
to run the drive in the reverse
direction.
B1
Customer Safeties
Sets the command to show that customer safeties are in place.
B2
BAS Interlock
Sets the command to show that the dampers are open.
B8
Low City Pressure
Sets the command to show that there is not sufficient pressure at the inlet to the pump.
OFF : Insufficient pressure is present on the inlet to the pump
Note:
When
Y1-01 = 3 [Multiplex Mode = Memobus Network]
, this function will activate on any drive in the network.
An alarm condition will cause other drives in the network to stop the operation and show a
“
Network Drive Error
”
“
Check Faulted Drive
”
message.
B9
Disable Pre-charge
Sets the command to disable the Pre-charge function.
ON : Pre-charge function is disabled
188
!Thermostat Fault
Sets the drive to show the
VLTS [Thermostat Fault]
when the input terminal is OFF.
Note:
This function is active when the drive is running.
1A8
!PI2 Control Disable
Sets the command to disable the PI2 Control function. Parameter
S3-12 [PI2 Control Disable Mode Sel]
sets the
output performance.
ON : Disabled
OFF : Enabled
1B8
!Low City Pressure
Sets the command to show that there is not sufficient pressure at the inlet to the pump.
ON : Insufficient pressure is present on the inlet to the pump
Note:
When
Y1-01 = 3 [Multiplex Mode = Memobus Network]
, this function will activate on any drive in the network.
An alarm condition will cause other drives in the network to stop the operation and show a
“
Network Drive Error
”
“
Check Faulted Drive
”
message.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...