450
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
■
S5-04: HAND-OFF-AUTO Behavior
No.
(Hex.)
Name
Description
Default
(Range)
S5-04
(3232)
HAND-OFF-AUTO
Behavior
Sets the drive behavior when the drive is in HAND Mode, OFF Mode, or AUTO Mode.
1
(0, 1)
0 : Legacy
1 : Normal
Note:
When you set this parameter to 1, the drive will always be in AUTO Mode when you energize the drive.
■
S5-05: HAND Frequency Reference
No.
(Hex.)
Name
Description
Default
(Range)
S5-05
(3233)
RUN
HAND Frequency Reference
Sets the frequency reference when HAND Mode is active, PID is disabled and
S5-01 = 1 [HAND
Frequency Reference Source = HAND Ref S5-05 or PID SP S5-06]
.
0.00 Hz
(0.00 - 400.00 Hz)
■
S5-06: HAND Setpoint
No.
(Hex.)
Name
Description
Default
(Range)
S5-06
(3234)
RUN
HAND Setpoint
Sets the System Setpoint when HAND Mode is active, PID is enabled and
S5-01 = 1 [HAND
Frequency Reference Source = HAND Ref S5-05 or PID SP S5-06]
.
0.0
(0.0 - 6000.0)
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-39 [PID User Unit Display Digits]
set the
unit, range, and resolution.
■
S5-07: Operation HAND Key
No.
(Hex.)
Name
Description
Default
(Range)
S5-07
(3235)
Operation HAND Key
Sets the HAND key on the HOA keypad to let you switch between HAND Mode and AUTO Mode.
1
(0, 1)
0 : Disabled
1 : Enabled
■
S5-08: HAND Reference Prime Loss Level
No.
(Hex.)
Name
Description
Default
(Range)
S5-08
(3D31)
RUN
HAND Reference Prime
Loss Level
Sets the level at which the drive will detect the Loss of Prime in the pump.
0.0
(0.0 - 1000.0)
Note:
•
If these conditions occur at the same time, the drive will detect
LOP [Loss of Prime]
:
–
The monitor set by
Y1-18 [Prime Loss Detection Method]
≤
S5-08
for longer than
Y1-20 [Prime Loss Time]
–
Output frequency ≥
S5-05 [HAND Frequency Reference]
•
The drive response to the Loss of Prime condition changes when the
Y1-22 [Prime Loss Selection]
setting changes.
•
Parameter
Y1-18 [Prime Loss Detection Method]
sets the units for this parameter.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...