2.2 A: Initialization Parameters
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
163
•
For general variable-speed control applications in which a high level of responsiveness or high-precision speed
control is not necessary.
•
To connect more than one motor to one drive
•
When there is not sufficient data to set the motor parameters
•
When it is not possible to do Auto-Tuning. The speed control range is 1:40.
5 : PM Open Loop Vector
The drive controls an IPM motor or SPM motor in this control method. Use this control method for general variable-
speed control applications in which a high level of responsiveness or high-precision speed control are not necessary.
The speed control range is 1:20.
8 : EZ Vector Control
The drive controls SynRM (Synchronous Reluctance Motors) in this control method. This control method uses an
easier procedure to operate motors with more efficiency. Use this control method for derating torque applications, for
example, fans and pumps.
■
A1-03: Initialize Parameters
No.
(Hex.)
Name
Description
Default
(Range)
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0
(0 - 3410)
Note:
•
After you initialize the drive, the drive automatically sets
A1-03 = 0
.
•
User Parameters can save the parameter values for your application and use these values as default values for drive initialization.
•
To use the 2 motor switchover function, first turn OFF the terminal to which
H1-xx = 16 [MFDI Function Selection = Motor 2 Selection]
is
set, then change the A1-03 setting. An incorrect procedure will trigger
oPE08 [Parameter Selection Error]
.
0 : No Initialization
1110 : User Initialization
Sets parameters to the values set by the user as user settings. Set
o2-03 = 1 [User Parameter Default Value = Set
defaults]
to save the user settings.
You can save the adjusted parameter settings from the test run as user-set default values to the drive. When you make
changes to the parameter values after you save the settings as User Parameter Settings, initialize with
A1-03 = 1110
for the drive to set the parameters to the User Parameter Setting value.
Follow this procedure to save User Parameter setting values and to do a User Initialization:
1. Set parameters correctly for the application.
2. Set
o2-03 = 1 [User Parameter Default Value = Set defaults]
.
This saves parameter settings for a User Initialization.
The drive will automatically set
o2-03 = 0
.
3. Set
A1-03 = 1110
to reset to the saved parameter settings.
When you initialize the drive, the drive sets the parameter values to the User Parameter setting values.
2220 : 2-Wire Initialization
Sets MFDI terminal S1 to Forward Run and terminal S2 to Reverse Run, and resets all parameters to default settings.
3330 : 3-Wire Initialization
Sets MFDI terminal S1 to Run, terminal S2 to Stop, and terminal S5 to FWD/REV, and resets all parameters to
default settings.
3410 : HVAC Initialization
Initializes the drive to factory default settings and then sets these parameters:
•
H1-03 = B1 [Terminal S3 Function Selection = Customer Safeties]
•
H1-04 = B2 [Terminal S4 Function Selection = BAS Interlock]
•
H1-05 = AF [Terminal S5 Function Selection = Emergency Override FWD]
•
H2-03 = B2 [Term M5-M6 Function Selection = BAS Interlock]
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...