216
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
b5-38:
b5-71:
U5-01:
Figure 2.28 Transducer Scaling Lower Limit
■
b5-82: Feedback Loss 4
~
20mA Detect Sel
No.
(Hex.)
Name
Description
Default
(Range)
b5-82
(31B0)
Feedback Loss 4
~
20mA
Detect Sel
Sets the drive to do a 4 to 20 mA wire-break detection on the analog input set for PID feedback.
2
(0 - 3)
0 : Disabled
Note:
Drives with
b5-82 = 0
and
Y9-02 ≠ 3 [System Feedback Source ≠ Network Only]
will not have feedback loss detection and will continuously
send the analog PID feedback to the network when the signal is good or bad.
1 : Alarm Only
2 : Fault
Note:
When
b5-82 = 2
and
Y9-02 ≠ 3
, PID feedback detection will trigger an alarm if one of these conditions is true:
•
The drive is in HAND Mode
•
There is no lead drive on the network
•
The drive is not in AUTO Mode
3 : Run At b5-83
Note:
If you enable Wire-Break detection, set
b5-83 [Feedback Loss GoTo Frequency]
<
Y9-09 [Staging Frequency Level]
, and set
b5-82 = 3
, and
you lose network feedback, the network will request for a de-stage. During an
FLGT [Feedback Loss, Go To Freq b5-83]
alarm, the lag
drives that are operating will continue to operate at the speed set in
Y9-05 [Lag Drive Mode]
.
If the drive detects a Wire-Break, the drive will respond as specified by
b5-82
.
Note:
•
A: The keypad shows an
FDBKL [Feedback Loss Wire Break]
alarm.
•
F: The drive detects an
FDBKL [WIRE Break]
fault.
•
R: The drive operates at
b5-83 [Feedback Loss GoTo Frequency]
and shows an
FDBKL
alarm.
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...