E : Const Trq, 60 Hz base, 180 Hz max
Use this constant output pattern to rotate motors at more than 60 Hz. Output voltage is constant when you operate at
more than 60 Hz.
Note:
The voltage values in the figures are for 208 V class drives. Multiply the values by 2 for 480 V class drives.
2011, 2017, 4005, 4008
2024 - 2169, 4011 - 4077
2211 - 2273, 4096 - 4302
F : Custom
Set
E1-04
to
E1-13 [V/f Pattern for Motor 1]
to set the values for this custom pattern.
The default settings are the same as setting value
1 [Const Trq, 60Hz base, 60Hz max]
.
■
E1-04: Maximum Output Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-04
(0303)
Maximum Output Frequency
Sets the maximum output frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(Determined by A1-02 and
E5-01)
■
E1-05: Maximum Output Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-05
(0304)
Maximum Output Voltage
Sets the maximum output voltage for the V/f pattern.
208 V Class: 230.0 V,
480 V Class: 460.0 V
(208 V Class: 0.0 - 255.0 V,
480 V Class: 0.0 - 510.0 V)
■
E1-06: Base Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(0.0 - E1-04)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...