TOEPYAIHV6002A HV600 Drive Programming
199
If you set this parameter too low, Speed Search will not operate correctly.
If the drive detects
oC [Overcurrent]
immediately after Speed Search Starts:
•
Increase the value of
L2-03 [Minimum Baseblock Time]
and decrease the motor speed you use to start Speed
Search.
•
Increases the setting value of
b3-08 [Speed Estimation ACR P Gain]
.
•
Increase the value of
b3-54
.
If the drive detects
oC
or
ov [DC Bus Overvoltage]
during Speed Search, increase the value of
b3-08
.
■
b3-55: Current Increment Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-55
(3124)
Expert
Current Increment Time
Sets the length of time that the drive will increase the current from zero current to the setting value of
b3-06 [Speed Estimation Current Level 1]
.
10 ms
(10 - 2000 ms)
Gradually increase the setting value when a large quantity of current flows after speed search starts. If you set this
value too high, speed search will not operate correctly.
■
b3-56: InverseRotationSearch WaitTime
No.
(Hex.)
Name
Description
Default
(Range)
b3-56
(3126)
InverseRotationSearch
WaitTime
Sets the wait time until the drive starts inverse rotation search after it completes forward search when
you do inverse rotation search during Current Detection Speed Search.
Determined by o2-04
(0.1 - 5.0 s)
◆
b4: Timer Function
The drive uses timers to delay activating and deactivating MFDO terminals.
Timers prevent sensors and switches from making chattering noise.
There are two types of timers:
•
Timers that set a delay for timer inputs and timer outputs.
These timers delay activating and deactivating of the MFDIs and MFDOs.
To enable this function, set
H1-xx = 18 [MFDI Function Select = Timer Function], and set H2-01 to H2-03 = 12
[MFDO Function Select = Timer Output]
.
•
Timers that set a delay to activate and deactivate MFDO terminals.
These timers delay activating and deactivating MFDO terminals.
To enable this function, set delay times in parameters
b4-03 to b4-08
.
■
Timer Function Operation
•
Timers that Set a Delay for Timer Inputs and Timer Outputs
Triggers timer output if the timer input is active for longer than the time set in
b4-01 [Timer Function ON-Delay
Time]
. Triggers timer output late for the time set in
b4-02 [Timer Function OFF-Delay Time]
.
shows an
example of how the timer function works.
Figure 2.22 Example of Timer Function Operation
•
Setting On/Off-delay Time for MFDO
uses H2-01 terminals to show an example of how the timer function works. Use
b4-03 [Terminal M1-
M2 ON-Delay Time]
and
b4-04 [Terminal M1-M2 OFF-Delay Time]
to set this function.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...