3.5 Items to Check before Starting Up the Drive
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
521
3.5
Items to Check before Starting Up the Drive
◆
Check before Energizing the Drive
Examine the items in
before you energize the drive.
Table 3.5 Items to Check before Energizing the Drive
Items to Check
Description
Input Power Supply Voltage
The voltage of the input power supply must be:
208 V class: three-phase 200 Vac to 240 Vac 50/60 Hz, 270 Vdc to 340 Vdc
480 V class: three-phase 380 Vac to 480 Vac 50/60 Hz, 510 Vdc to 680 Vdc
Correctly and safely wire power supply input terminals R/L1, S/L2, T/L3.
Correctly ground the drive and motor.
Connection between Drive Output
Terminals and Motor Terminals
Make sure that you connected drive output terminals U/T1, V/T2, and W/T3 in the correct sequence to agree with motor terminals U, V,
and W without loosened screws.
Control Circuit Terminal Wiring
Make sure that you connected the drive control circuit terminals in the correct sequence to agree with devices and switches without
loosened screws.
Control Circuit Terminal Status
Turn OFF the inputs from all devices and switches connected to the drive control circuit terminals.
Connection between Machinery and Motor
Disengage all couplings and belts that connect the motor and machinery.
◆
Check after Energizing the Drive
Examine the items in
after you energize the drive. The keypad will show these screens depending on the
drive status.
Table 3.6 Display Status after Energizing the Drive
Status
Display
Description
During Usual Operation
Initial Setup Screen
or
HOME Screen
•
The data display area will show the Initial Setup screen or the HOME screen
•
Energize the drive with factory defaults to show the Initial Setup screen. Select [No]
from the [Show Initial Setup Screen] settings to show the HOME screen without
showing the Initial Setup screen.
When the Drive Detects a Fault
The display changes depending on the fault. Refer to
“
Troubleshooting
”
to remove the
cause of the fault.
will illuminate.
Note:
If the screen shows a different screen, do these steps to show the fault content again:
1.
Push
from the HOME screen.
2.
Push
(Home) from a different screen than the HOME screen.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...