440
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
8 : Friday
9 : Saturday
10 : Sunday
■
S2-19: Timer 4 Sequence Selection
No.
(Hex.)
Name
Description
Default
(Range)
S2-19
(3218)
Timer 4 Sequence Selection
Sets the drive response when sequence timer 4 is active.
0
(0 - 3)
0 : Digital Out Only
1 : Run
2 : Run - PID Disable
3 : Allow Alternation
■
S2-20: Timer 4 Reference Source
No.
(Hex.)
Name
Description
Default
(Range)
S2-20
(3219)
Timer 4 Reference Source
Selects the frequency reference source to run the drive when sequence timer 4 is active (only
applicable when
S2-19 > 0 [Timer 4 Sequence Selection ≠ Digital Out Only]
).
0
(0 - 8)
0 : Operator (d1-01/YA-01)
1 : Operator (d1-02/YA-02)
2 : Operator (d1-03/YA-03)
3 : Operator (d1-04/YA-04)
4 : Terminals
5 : Serial Com
6 : Option PCB
8 : Set by b1-01
Note:
For reference source 0 to 3, the drive will use
d1-xx
frequency reference when PID mode is disabled and
YA-xx
setpoint when PID is enabled.
◆
S3: PI2 Control
S3 parameters
set the PI2 Control function. You can use this function to monitor the input, setpoint, feedback and
output levels of the PI2 Control through several additional monitors. You can also set the drive to activate certain
MFDO terminals when the PI2 feedback level is less than or more than a set value. The difference between the target
and the feedback value (deviation) is fed into the PI controller and the PI controller outputs the frequency to
U5-xx
for
monitoring. Refer to
for more information.
■
PI2 Control Setpoint and Feedback
PI2 Control has three ways to set the target setpoint. This is the order of the input setpoints from most important to
least important:
1. MEMOBUS setpoint: 000DH (while 000FH, bit 4 = 1)
2. Analog setpoint:
H3-xx = 25 [MFAI Function Selection = PI2 Control Setpoint]
3. Digital setpoint:
S3-05 [PI2 Control Setpoint]
For the feedback, PI2 Control only has analog setting
H3-xx = 26 [PI2 Control Feedback]
as the feedback level.
■
PI2 Control Monitors
These monitors will work as the PI2 Control monitors for the setpoint, feedback, input, and output:
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...