234
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
C6-03:
C6-04:
C6-05:
E1-04:
Figure 2.36 Setting a Variable Carrier Frequency to Agree with the Output Frequency
Note:
•
When
C6-05 ≤ 7
, the drive disables
C6-04
. The carrier frequency is fixed to the value set to
C6-03
.
•
If these conditions are true at the same time, the drive will detect
oPE11 [Carrier Frequency Setting Error]
:
–
C6-05 ≥ 6
–
C6-04 ≥ C6-03
■
C6-04: Carrier Frequency Lower Limit
No.
(Hex.)
Name
Description
Default
(Range)
C6-04
(0226)
Carrier Frequency Lower
Limit
Sets the lower limit of the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(1.0 - 12.5 kHz)
Set
C6-03 [Carrier Frequency Upper Limit]
,
C6-04
, and
C6-05 [Carrier Freq Proportional Gain]
to make the carrier
frequency change linearly with the output frequency.
Note:
If these conditions are true at the same time, the drive will detect
oPE11 [Carrier Frequency Setting Error]
:
•
C6-04 ≥ C6-03
•
C6-05 ≥ 6
■
C6-05: Carrier Freq Proportional Gain
No.
(Hex.)
Name
Description
Default
(Range)
C6-05
(0227)
Carrier Freq Proportional
Gain
Sets the proportional gain for the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection =
User Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(0 - 99)
Set
C6-03 [Carrier Frequency Upper Limit]
,
C6-04 [Carrier Frequency Lower Limit]
, and
C6-05
to make the carrier
frequency change linearly with the output frequency.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...