292
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
Setting
Signal Input Method from
Peripheral Devices
External Fault Detection Method
Stopping Method
N.O.
N.C.
Always
Detected
Detected during
RUN Only
Ramp to Stop
(Fault)
Coast to Stop
(Fault)
Fast Stop
(Fault)
Continuous
Operation
(Alarm Only)
2A
x
-
-
x
-
-
x
-
2B
-
x
-
x
-
-
x
-
2C
x
-
x
-
-
-
-
x
2D
-
x
x
-
-
-
-
x
2E
x
-
-
x
-
-
-
x
2F
-
x
-
x
-
-
-
x
*1
Set the terminal to N.O. (detects external fault when switched ON) or N.C. (detects external fault when switched OFF).
*2
Set the drive to always detect each fault or to detect only during run.
■
30: PID Integrator Reset
Setting Value
Function
Description
30
PID Integrator Reset
Sets the command to reset and hold the PID control integral to 0 when the terminal is ON.
Note:
Refer to
“
PID control block diagram
”
for more information.
■
31: PID Integrator Hold
Setting Value
Function
Description
31
PID Integrator Hold
Sets the command to hold the integral value of the PID control while the terminal is activated.
When you turn off the input terminal, PID control restarts the integral.
Note:
Refer to
“
PID control block diagram
”
for more information.
■
34: PID Soft Starter Disable
Setting Value
Function
Description
34
PID Soft Starter Disable
Sets the PID soft starter function.
ON : Disabled
Disables
b5-17 [PID Accel/Decel Time]
.
OFF : Enabled
Enables
b5-17 [PID Accel/Decel Time]
.
Note:
Refer to
“
PID control block diagram
”
for more information.
■
35: PID Input (Error) Invert
Setting Value
Function
Description
35
PID Input (Error) Invert
Sets the command to turn the terminal ON and OFF to switch the PID input level (polarity).
Note:
Refer to
“
PID control block diagram
”
for more information.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...