YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
591
Table 4.4 Control Circuit Output Terminals
Type
Terminal
Name (Default)
Function (Signal Level)
Fault Relay
Output
MA
N.O. output
(Fault)
Drive Fault Signal Output
•
Relay output
•
30 Vdc, 10 mA to 2 A
•
250 Vac, 10 mA to 2 A
•
Minimum load: 5 V, 10 mA (Reference value)
MB
N.C. output
(Fault)
MC
Digital output common
MFDO
M1
MFDO
(During Run)
Multi Function Digital Output
•
Relay output
•
30 Vdc, 10 mA to 2 A
•
250 Vac, 10 mA to 2 A
•
Minimum load: 5 V, 10 mA (Reference value)
Note:
Do not set functions that frequently switch ON/OFF to MFDO (M1 to M6) because this will
decrease the performance life of the relay contacts. Yaskawa estimates switching life at
200,000 times (assumes 1 A, resistive load).
M2
M3
MFDO
(Zero Speed)
M4
M5
MFDO
(Speed Agree 1)
M6
Table 4.5 Control Circuit Monitor Output Terminals
Type
Terminal
Name (Default)
Function (Signal Level)
Monitor Output
FM
MFAO 1
(Output frequency)
Multi Function Analog Output
Select voltage or current output.
•
0 V to 10 V/0% to 100%
•
4 mA to 20 mA (receiver recommended impedance: 250 Ω)
Note:
Select with jumper switch S5 and
H4-07 [Terminal FM Signal Level Select]
or
H4-08
[Terminal AM Signal Level Select]
.
AM
MFAO 2
(Output current)
AC
Monitor common
0 V
External Power
Supply Output
+P
External power supply
Power supply for external devices.
•
24 V (150 mA maximum)
■
External Power Supply Input Terminals
Refer to
for a list of the functions of the external power supply input terminals.
Table 4.6 External Power Supply Input Terminals
Type
Terminal
Name (Default)
Function
External Power Supply Input
Terminals
PS
External 24 V power supply input
Supplies backup power to the drive control circuit, keypad, and option board.
21.6 VDC to 26.4 VDC, 700 mA
AC
External 24 V power supply ground
0 V
Alarm Display When You Use External 24 V Power Supply
When you use an external 24 V power supply, the drive detects an alarm as shown in
if you set
o2-23
[External 24V Powerloss Detection]
and
o2-26 [Alarm Display at Ext. 24V Power]
for the main circuit power supply.
Set the alarm display as necessary.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...