YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
61
Setting Value
Function
Description
Ref.
8
During Baseblock (N.O.)
The terminal activates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : During baseblock
OFF : The drive is not in baseblock.
9
Frequency Reference
from Keypad
Shows the selected frequency reference source.
ON : The keypad is the frequency reference source.
OFF : Parameter
b1-01 [Frequency Reference Selection 1]
is the frequency reference source.
B
Torque Detection 1 (N.
O.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque >
L6-02 [Torque Detection Level 1]
, or the output current/torque <
L6-02
for longer
than the time set in
L6-03 [Torque Detection Time 1]
.
C
Frequency Reference
Loss
The terminal activates when the drive detects a loss of frequency reference.
E
Fault
The terminal activates when the drive detects a fault.
Note:
The terminal will not activate for
CPF00
and
CPF01 [Control Circuit Error]
faults.
F
Not Used
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact
output via MEMOBUS/Modbus or the communication option. This signal does not function if you do not configure
signals from the PLC.
10
Alarm
The terminal activates when the drive detects a minor fault.
11
Fault Reset Command
Active
The terminal activates when the drive receives the Reset command from the control circuit terminal, serial
communications, or the communication option.
12
Timer Output
Use this setting when the drive uses the timer function as an output terminal.
13
Speed Agree 2
The terminal activates when the output frequency is in the range of the frequency reference ±
L4-04 [Speed Agree
Detection Width (+/-)]
.
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of
“
frequency reference ±
L4-04
”
.
OFF : The output frequency is not in the range of
“
frequency reference ±
L4-04
”
.
14
User-Set Speed Agree 2
The terminal activates when the output frequency is in the range of
L4-03 [Speed Agree Detection Level (+/-)]
±
L4-04
[Speed Agree Detection Width (+/-)]
and in the range of the frequency reference ±
L4-04
.
Note:
The detection level set in
L4-03
is a signed value. The drive will only detect in one direction.
ON : The output frequency is in the range of
“
L4-03
±
L4-04
”
and the range of frequency reference ±
L4-04
.
OFF : The output frequency is not in the range of
“
L4-03
±
L4-04
”
or the range of frequency reference ±
L4-04
.
15
Frequency Detection 3
The terminal deactivates when the output frequency >
“
L4-03 [Speed Agree Detection Level (+/-)]
+
L4-04 [Speed
Agree Detection Width (+/-)]
”
. After the terminal deactivates, the terminal stays deactivated until the output frequency
is at the value of
L4-03
.
Note:
The detection level set in
L4-03
is a signed value. The drive will only detect in one direction.
ON : The output frequency <
L4-03
, or the output frequency ≤
L4-03
+
L4-04
.
OFF : The output frequency >
“
L4-03
+
L4-04
”
.
16
Frequency Detection 4
The terminal activates when the output frequency >
L4-03 [Speed Agree Detection Level (+/-)]
. After the terminal
activates, the terminal stays activated until the output frequency is at the value of
“
L4-03
-
L4-04
”
.
Note:
The detection level set in
L4-03
is a signed value. The drive will only detect in one direction.
ON : The output frequency >
L4-03
.
OFF : The output frequency <
“
L4-03
-
L4-04
”
, or the output frequency ≤
L4-03
.
17
Torque Detection 1 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque >
L6-02 [Torque Detection Level 1]
, or the output current/torque <
L6-02
for longer
than the time set in
L6-03 [Torque Detection Time 1]
.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...