YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
315
ON : The output frequency >
L4-03
.
OFF : The output frequency < “
L4-03
-
L4-04
”, or the output frequency
≤
L4-03
.
L4-03:
L4-04:
Figure 2.68 Example of Frequency Detection 4 (Value of L4-03 is Positive)
■
17: Torque Detection 1 (N.C.)
Setting Value
Function
Description
17
Torque Detection 1 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
OFF : The output current/torque >
L6-02 [Torque Detection Level 1]
, or the output current/torque <
L6-02
for longer than the time set in
L6-03 [Torque Detection Time 1]
.
Note:
•
When
L6-01 ≥ 5
, the drive will detect when the output current/torque is less than
L6-02
for longer than
L6-03
.
•
Refer to
L6: Torque Detection on page 375
for more information.
■
18: Torque Detection 2 (N.O.)
Setting Value
Function
Description
18
Torque Detection 2 (N.O.)
The terminal activates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
ON : The output current/torque >
L6-05 [Torque Detection Level 2]
, or the output current/torque <
L6-
05
for longer than the time set in
L6-06 [Torque Detection Time 2]
.
Note:
•
When
L6-04 ≥ 5
, the drive will detect when the output current/torque is less than
L6-05
for longer than
L6-06
.
•
Refer to
L6: Torque Detection on page 375
for more information.
■
19: Torque Detection 2 (N.C.)
Setting Value
Function
Description
19
Torque Detection 2 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
OFF : The output current/torque >
L6-05 [Torque Detection Level 2]
, or the output current/torque <
L6-05
for longer than the time set in
L6-06 [Torque Detection Time 2]
.
Note:
•
When
L6-04 ≥ 5
, the drive will detect when the output current/torque is less than
L6-05
for longer than
L6-06
.
•
Refer to
L6: Torque Detection on page 375
for more information.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...