0 : No Retry
1 : Retry
■
L5-51: Loss of Prime Fault Retry Select
No.
(Hex.)
Name
Description
Default
(Range)
L5-51
(367B)
Loss of Prime Fault Retry
Select
Sets the drive to try an Auto Restart if it detects an
LOP [Loss Of Prime]
fault.
0
(0, 1)
0 : No Retry
1 : Retry
■
L5-53: Thermostat Fault Retry Selection
No.
(Hex.)
Name
Description
Default
(Range)
L5-53
(3251)
Thermostat Fault Retry
Selection
Sets the drive to try an Auto Restart if it detects a
VLTS [Thermostat Fault]
fault.
1
(0, 1)
Note:
•
To use this function, set
S5-01 ≠ 0 [HAND Frequency Reference Source ≠ HAND Analog Input]
•
The drive will only restart after the Thermostat digital input deactivates and the
L5-04 [Interval Method Restart Time]
timer is expired.
0 : No Retry
1 : Retry
shows the drive operation for
VLTS
when
L5-53 = 1
and
L5-01 [Number of Auto-Restart Attempts] > 0
times
. The drive will wait for the Thermostat digital input to deac the
L5-04
time before it will restart.
H1-xx = 188:
H2-xx = 95:
L5-04:
VLTS Fault:
Figure 2.101 Thermostat Fault Behavior
◆
L6: Torque Detection
The overtorque/undertorque/underload detection function prevents damage to machinery and loads.
Overtorque is when there is too much load on the machine. If the motor current or output torque is at the overtorque
detection level for the overtorque detection time, the drive will output an alarm and turn off the output.
Undertorque and underload are when a load suddenly decreases. When the motor current or output torque is at the
undertorque/underload detection level for the undertorque detection time, the drive will output an alarm and turn off
the output.
You can use the undertorque/underload detection function to detect these conditions, for example:
•
Machine belt breaks
•
Unusual operation of the electromagnetic contactor on the drive output side
•
Clogged output side air filters in fans and blowers
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...