312
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
■
B: Torque Detection 1 (N.O.)
Setting Value
Function
Description
B
Torque Detection 1 (N.O.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque >
L6-02 [Torque Detection Level 1]
, or the output current/torque <
L6-
02
for longer than the time set in
L6-03 [Torque Detection Time 1]
.
Note:
•
When
L6-01 ≥ 5
, the drive will detect when the output current/torque is less than
L6-02
for longer than
L6-03
.
•
Refer to
L6: Torque Detection on page 375
for more information.
■
C: Frequency Reference Loss
Setting Value
Function
Description
C
Frequency Reference Loss
The terminal activates when the drive detects a loss of frequency reference.
Note:
Refer to
“
L4-05: Fref Loss Detection Selection
”
for more information.
■
E: Fault
Setting Value
Function
Description
E
Fault
The terminal activates when the drive detects a fault.
Note:
The terminal will not activate for
CPF00
and
CPF01 [Control Circuit Error]
faults.
■
F: Not Used
Setting Value
Function
Description
F
Not Used
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact output via
MEMOBUS/Modbus or the communication option. This signal does not function if you do not configure signals from the PLC.
■
10: Alarm
Setting Value
Function
Description
10
Alarm
The terminal activates when the drive detects a minor fault.
■
11: Fault Reset Command Active
Setting Value
Function
Description
11
Fault Reset Command
Active
The terminal activates when the drive receives the Reset command from the control circuit terminal, serial communications, or the
communication option.
■
12: Timer Output
Setting Value
Function
Description
12
Timer Output
Use this setting when the drive uses the timer function as an output terminal.
Note:
Refer to
Timer Function Operation on page 199
for more information.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...