TOEPYAIHV6002A HV600 Drive Programming
117
No.
(Hex.)
Name
Description
MFAO Signal Level
U2-21
(1166)
Expert
STPo Detect @ Fault
Monitors conditions to detect
STPo [Motor Step-Out Detected]
faults. The bit for each condition is
shown as ON or OFF.
bit0 : Excessive current
bit1 : Induced voltage deviation
bit2 : d-axis current deviation
bit3 : Motor lock at startup
bit4 : Acceleration stall continue
bit5 : Acceleration stall repeat
bit6 : Not used (normal value of 0).
bit7 : Not used (normal value of 0).
No signal output available
U2-30
(3008)
Fault 1 YYYY
Shows the year when the most recent fault occurred.
No signal output available
U2-31
(3009)
Fault 1 MMDD
Shows the month and day when the most recent fault occurred.
No signal output available
U2-32
(300A)
Fault 1 HHMM
Shows the time when the most recent fault occurred.
No signal output available
◆
U3: Fault History
No.
(Hex.)
Name
Description
MFAO Signal Level
U3-01
(0090)
1st MostRecent Fault
Shows the fault history of the most recent fault.
Note:
The drive saves this fault history to two types of registers at the same time for the MEMOBUS/
Modbus communications.
No signal output available
U3-02
(0091)
2nd MostRecent Fault
Shows the fault history of the second most recent fault.
Note:
The drive saves this fault history to two types of registers at the same time for the MEMOBUS/
Modbus communications.
No signal output available
U3-03
(0092)
3rd MostRecent Fault
Shows the fault history of the third most recent fault.
Note:
The drive saves this fault history to two types of registers at the same time for the MEMOBUS/
Modbus communications.
No signal output available
U3-04
(0093)
4th MostRecent Fault
Shows the fault history of the fourth most recent fault.
Note:
The drive saves this fault history to two types of registers at the same time for the MEMOBUS/
Modbus communications.
No signal output available
U3-05
(0804)
5th MostRecent Fault
Shows the fault history of the fifth most recent fault.
No signal output available
U3-06
(0805)
6th MostRecent Fault
Shows the fault history of the sixth most recent fault.
No signal output available
U3-07
(0806)
7th MostRecent Fault
Shows the fault history of the seventh most recent fault.
No signal output available
U3-08
(0807)
8th MostRecent Fault
Shows the fault history of the eighth most recent fault.
No signal output available
U3-09
(0808)
9th MostRecent Fault
Shows the fault history of the ninth most recent fault.
No signal output available
U3-10
(0809)
10th MostRecentFault
Shows the fault history of the tenth most recent fault.
No signal output available
U3-11
(0094)
ElapsedTime@1stFault
Shows the cumulative operation time when the most recent fault occurred.
Note:
The drive saves this cumulative operation time to two types of registers at the same time for the
MEMOBUS/Modbus communications.
Unit: 1 h
No signal output available
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...