TOEPYAIHV6002A HV600 Drive Programming
Note:
The voltage values in the figures are for 208 V class drives. Multiply the values by 2 for 480 V class drives.
2011, 2017, 4005, 4008
2024 - 2169, 4011 - 4077
2211 - 2273, 4096 - 4302
B : High Trq, 60Hz, 65% Vmin boost
Use this pattern when high torque is necessary during start up.
Select this pattern only in these conditions:
•
The wiring distance between the drive and motor is 150 m (492.1 ft) minimum.
•
There is an AC reactor connected to the drive output.
Note:
The voltage values in the figures are for 208 V class drives. Multiply the values by 2 for 480 V class drives.
2011, 2017, 4005, 4008
2024 - 2169, 4011 - 4077
2211 - 2273, 4096 - 4302
C : High Freq, 60Hz base, 90Hz max
Use this constant output pattern to rotate motors at more than 60 Hz. Output voltage is constant when you operate at
more than 60 Hz.
Note:
The voltage values in the figures are for 208 V class drives. Multiply the values by 2 for 480 V class drives.
2011, 2017, 4005, 4008
2024 - 2169, 4011 - 4077
2211 - 2273, 4096 - 4302
D : Const Trq, 60 Hz base, 120 Hz max
Use this constant output pattern to rotate motors at more than 60 Hz. Output voltage is constant when you operate at
more than 60 Hz.
Note:
The voltage values in the figures are for 208 V class drives. Multiply the values by 2 for 480 V class drives.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...