YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
73
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H4-03
(041F)
RUN
Terminal FM Analog
Output Bias
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
Set the level of the analog signal sent from terminal FM at 10 V or 20 mA as 100% when
an output for monitoring items is 0%.
0.0%
(-999.9 - +999.9%)
H4-04
(0420)
Terminal AM Analog
Output Select
Sets the monitoring number to be output from the MFAO terminal AM.
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H4-04 = 103
to monitor
U1-03
[Output Current]
.
103
(000 - 999)
H4-05
(0421)
RUN
Terminal AM Analog
Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output
level from the AM terminal at 10 V or 20 mA as 100%.
50.0%
(-999.9 - +999.9%)
H4-06
(0422)
RUN
Terminal AM Analog
Output Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output
level from the AM terminal at 10 V or 20 mA as 0%.
0.0%
(-999.9 - +999.9%)
H4-07
(0423)
Terminal FM Signal
Level Select
Sets the MFAO terminal FM output signal level.
Note:
Set jumper S5 on the control circuit terminal block accordingly when you change this
parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
0
(0, 2)
H4-08
(0424)
Terminal AM Signal
Level Select
Sets the MFAO terminal AM output signal level.
Note:
Set jumper S5 on the control circuit terminal block accordingly when you change this
parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
0
(0, 2)
H4-20
(0B53)
Analog Power Monitor
100% Level
Sets the level at 10 V when you set
U1-08 [Output Power]
for analog output.
0.00 kW
(0.00 - 650.00 kW)
◆
H5: Serial Communication
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H5-01
(0425)
Drive Node Address
Sets the communication slave address for drives.
Note:
•
Restart the drive after you change the parameter setting.
•
Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
•
When
Y1-01 = 3 [Multiplex Mode = Memobus Network]
, the setting range changes
when the
Y9-25 [Highest Node Address]
setting changes.
1FH
(0 - FFH)
H5-02
(0426)
Communication Speed
Selection
Sets the communications speed for MEMOBUS/Modbus communications.
Note:
Re-energize the drive or set
H5-20 = 1 [Communication Parameters Reload = Reload
Now]
after you change the parameter setting.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
3
(0 - 8)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...