82
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L5-49
(3679)
Fault Retry Speed Search
Select
Sets the drive to do a speed search at the start of a Fault Retry.
0 : Disabled
1 : Enabled
1
(0, 1)
L5-50
(367A)
Setpoint Not Met Fault
Retry Sel
Sets the drive to try an Auto Restart when it detects an
NMS [SetPoint Not Met]
fault.
0 : No Retry
1 : Retry
0
(0, 1)
L5-51
(367B)
Loss of Prime Fault Retry
Select
Sets the drive to try an Auto Restart if it detects an
LOP [Loss Of Prime]
fault.
0 : No Retry
1 : Retry
0
(0, 1)
L5-53
(3251)
Thermostat Fault Retry
Selection
Sets the drive to try an Auto Restart if it detects a
VLTS [Thermostat Fault]
fault.
Note:
•
To use this function, set
S5-01 ≠ 0 [HAND Frequency Reference Source ≠ HAND
Analog Input]
•
The drive will only restart after the Thermostat digital input de-activates and the
L5-
04 [Interval Method Restart Time]
timer is expired.
0 : No Retry
1 : Retry
1
(0, 1)
◆
L6: Torque Detection
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L6-01
(04A1)
Torque Detection
Selection 1
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
0 : Disabled
1 : oL @ Speed Agree - Alarm only
2 : oL @ RUN - Alarm only
3 : oL @ Speed Agree - Fault
4 : oL @ RUN - Fault
5 : UL @ Speed Agree - Alarm only
6 : UL @ RUN - Alarm only
7 : UL @ Speed Agree - Fault
8 : UL @ RUN - Fault
9 : UL6 @ Speed Agree - Alarm only
10 : UL6 @ RUN - Alarm only
11 : UL6 @ Speed Agree - Fault
12 : UL6 @ RUN - Fault
0
(0 - 12)
L6-02
(04A2)
Torque Detection Level 1
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated
output current = 100% value. In vector control, motor rated torque = 100% value.
15%
(0 - 300%)
L6-03
(04A3)
Torque Detection Time 1
Sets the detection time for Overtorque/Undertorque Detection 1.
10.0 s
(0.0 - 10.0 s)
L6-04
(04A4)
Torque Detection
Selection 2
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
0 : Disabled
1 : oL @ Speed Agree - Alarm only
2 : oL @ RUN - Alarm only
3 : oL @ Speed Agree - Fault
4 : oL @ RUN - Fault
5 : UL @ Speed Agree - Alarm only
6 : UL @ RUN - Alarm only
7 : UL @ Speed Agree - Fault
8 : UL @ RUN - Fault
0
(0 - 8)
L6-05
(04A5)
Torque Detection Level 2
Sets the detection level for Overtorque/Undertorque Detection 2. In V/f control, drive rated
output current = 100% value. In vector control, motor rated torque = 100% value.
150%
(0 - 300%)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...