KEB Operation Wiring Example
shows an example that uses an undervoltage relay to trigger the KEB Ride-Thru at power loss. When a
power loss occurs, the undervoltage relay triggers
KEB Ride-Thru [H1-06 = 65, 66, 7A, 7B]
at terminal S6.
Note:
Configure the drive to turn ON the Run command while the KEB function is operating. If you turn off the Run command, the drive will not
accelerate back to speed when you return power.
Figure 2.86 KEB Function Wiring Example
■
Parameters for KEB Ride-Thru
shows the parameters that adjust the KEB Ride-Thru function. Parameter settings are different for the
different KEB methods set in
L2-29 [Kinetic Energy Backup Method]
.
Table 2.58 Parameters for KEB Ride-Thru
No.
Name
Settings
L2-29 [Kinetic Energy
Backup Method]
0
1
C1-09
Fast Stop Time
•
If
ov [Overvoltage]
occurs during KEB deceleration, increase the setting value.
•
If
Uv1 [DC Bus Undervoltage]
occurs during KEB deceleration, decrease the setting value.
-
C2-03
S-Curve Time @ Start of Decel
•
If
ov
occurs immediately after you start KEB deceleration, increase the setting value.
•
If
Uv1
occurs immediately after you start KEB deceleration, decrease the setting value.
x
-
L2-05
Undervoltage Detection Lvl (Uv1)
If
Uv1
occurs immediately after you start KEB deceleration, increase the setting value to detect
power loss more quickly.
x
x
L2-06
Does KEB Tuning.
•
Kinetic Energy Backup Decel Time
•
If
ov
or
Uv1
occur during KEB deceleration after KEB Tuning, set
L2-06
in these conditions:
–
If
ov
occurs, increase the setting value
–
If
Uv1
occurs, decrease the setting value.
-
-
L2-07
Kinetic Energy Backup Accel Time Sets the acceleration time to return to the frequency reference value before a power loss, after
you cancel the KEB operation. When
L2-07 = 0
, the drive uses the standard acceleration times
set in
C1-01 and C1-03
.
x
x
L2-08
Frequency Gain at KEB Start
•
If
ov
occurs immediately after you start operation, decrease the setting value.
•
If
Uv1
occurs immediately after you start operation, increase the setting value.
x
-
L2-10
Minimum KEB Time
•
With KEB Ride-Thru
There is
Uv1
because you set a digital input for KEB Ride-Thru and the device that controls
the input operated too slowly after power loss.
•
Without KEB Ride-Thru
If the DC bus voltage overshoots immediately after KEB Ride-Thru starts, increase
L2-10
to
longer than the overshoot.
x
x
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...