356
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
No.
Name
Settings
L2-29 [Kinetic Energy
Backup Method]
0
1
L2-11
KEB DC Bus Voltage Setpoint
•
Single Drive KEB Ride-Thru 2
Set to approximately 1.22 × input voltage.
•
Single Drive KEB Ride-Thru 1
Set to approximately 1.4 × input voltage.
x
x
L3-20
DC Bus Voltage Adjustment Gain
•
If
ov
or
Uv1
occurs at the start of deceleration when you use KEB operation, increase this
value in 0.1-unit increments.
•
If there is torque ripple during deceleration when you use KEB Ride-Thru, decrease the value.
-
x
L3-21
OVSuppression Accel/Decel P Gain If there is large speed or current ripple, decrease the value in 0.05 unit increments.
Note:
If the setting value is too low, then the drive will have unsatisfactory DC bus voltage control
response. The drive can detect
ov
or
Uv1
.
-
x
L3-24
Motor Accel Time @ Rated Torque Set the motor acceleration time to the maximum frequency at the motor rated torque.
-
x
L3-25
Load Inertia Ratio
Sets the ratio between motor inertia and machine inertia.
-
x
*1
When
L2-29 = 0 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 1]
and you do KEB Auto-Tuning, the drive will
automatically set
C1-09
. If you must not change the Fast Stop time, do not do KEB Tuning.
*2
The drive sets this value automatically when KEB Tuning completes correctly.
■
L2-01: Power Loss Ride Through Select
No.
(Hex.)
Name
Description
Default
(Range)
L2-01
(0485)
Power Loss Ride Through
Select
Sets the drive operation after a momentary power loss.
2
(0 - 2)
The drive detects momentary power loss when the drive DC bus voltage is less than the value set in
L2-05
[Undervoltage Detection Lvl (Uv1)]
.
0 : Disabled
The drive detects
Uv1 [DC Bus Undervoltage]
when a there is a momentary power loss.
If you do not return power in 15 ms, it triggers
Uv1
and the drive shuts off the output. The motor coasts to stop.
1 : Enabled for L2-02 Time
When power returns in the time set in
L2-02 [Power Loss Ride Through Time]
, the drive will restart. If power does
not return in the time set in
L2-02
, the drive will detect
Uv1
.
The drive momentarily turns OFF its output after a power loss. If the power returns in the time set to
L2-02
, the drive
will do Speed Search and try to continue operation.
If the DC bus voltage is less than or equal to the
Uv1
detection level for the time set in
L2-02
, the drive will detect
Uv1
and output a fault signal.
Note:
•
The necessary time for the drive to restart after power returns is different for different drive capacities.
•
The upper limit of the possible momentary power loss Ride-Thru time is different for different drive models.
2 : Enabled while CPU Power Active
When power returns and the drive control circuit has power, the drive will restart. This will not trigger
Uv1
.
When there is a momentary power loss, the drive output will turn OFF. If the power returns and the drive control
circuit has power, the drive will do Speed Search and try to continue operation. This will not trigger a
Uv1
. This
function enables longer support for power loss than when
L2-01 = 1
.
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...