YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
563
Input Data
Parameter
Unit
Auto-Tuning Mode
(T2-01 Setting)
PM Motor Parameter Settings
(0)
PM Stationary Auto-
Tuning
(1)
PM Stationary Auto-
Tuning for Stator
Resistance
(2)
Control Method Selection
A1-02
-
5
5
5
PM Motor Code Selection
T2-02
-
Motor Code of
Yaskawa Motor
-
-
Back-EMF Voltage Constant (Ke)
T2-14
x
x
-
-
Pull-In Current Level
T2-15
%
-
-
x
-
*1
Set the motor code for a Yaskawa PM motor.
*2
Set the motor code to FFFF for a PM motor from a different manufacturer.
*3
Changes when the value set in
T2-13
changes.
Table 3.11 Input Data for PM Motor Auto-Tuning
Input Data
Parameter
Unit
Auto-Tuning Mode
(T2-01 Setting)
PM Rotational Auto-Tuning
(4)
High Frequency Injection
Auto-Tuning
(5)
Control Method Selection
A1-02
-
5
5
PM Motor Code Selection
T2-02
-
-
-
PM Motor Type
T2-03
-
x
-
PM Motor Rated Power
T2-04
kW
x
-
PM Motor Rated Voltage
T2-05
V
x
-
PM Motor Rated Current
T2-06
A
x
-
PM Motor Base Frequency
T2-07
Hz
x
-
Number of PM Motor Poles
T2-08
-
x
-
PM Motor Stator Resistance
T2-10
Ω
-
-
PM Motor d-Axis Inductance
T2-11
mH
-
-
PM Motor q-Axis Inductance
T2-12
mH
-
-
Back-EMF Units Selection
T2-13
-
-
-
Back-EMF Voltage Constant (Ke)
T2-14
-
-
Pull-In Current Level
T2-15
%
x
-
*1
Changes when the value set in
T2-13
changes.
◆
Auto-Tuning in EZ Open Loop Vector Control Method
This section gives information about the Auto-Tuning mode for EZ Open Loop Vector Control. Auto-Tuning will set
the
E9-xx
parameters.
Table 3.12 EZ Tuning Mode Selection
Mode
Parameter
Settings
Application Conditions and Benefits
Applicable Control Method
(A1-02 Setting)
Motor Parameter Setting
T4-01 = 0
•
Applicable when driving SynRM (Synchronous Reluctance
Motors).
•
Suitable for derating torque applications, for example fans and
pumps.
EZOLV
(8)
Line-to-Line Resistance
T4-01 = 1
•
After Auto-Tuning, the wiring distance between the drive and
motor changed by 50 m or more.
•
When the motor output and drive capacity are different.
EZOLV
(8)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...