YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
195
Note:
When the drive cannot accurately estimate the speed after you adjust this parameter, use Current Detection Speed Search.
■
b3-07: Speed Estimation Current Level 2
No.
(Hex.)
Name
Description
Default
(Range)
b3-07
(0197)
Expert
Speed Estimation Current
Level 2
Sets the level of current that flows to the motor during Speed Estimation Speed Search as a
coefficient of
E2-03 [Motor No-Load Current]
or
E4-03 [Motor 2 Rated No-Load Current]
. Usually
it is not necessary to change this setting.
1.0
(0.0 - 3.0)
During Speed Estimation Speed Searches, when the speed estimation value aligns with the minimum output
frequency, increase the setting value in 0.1-unit increments. The limit of the output current during speed search is
automatically the drive rated current.
■
b3-08: Speed Estimation ACR P Gain
No.
(Hex.)
Name
Description
Default
(Range)
b3-08
(0198)
Speed Estimation ACR P
Gain
Sets the proportional gain for the automatic current regulator during Speed Estimation Speed Search.
Also adjusts speed search responsiveness. Usually it is not necessary to change this setting.
Determined by A1-02 and
o2-04
(0.00 - 6.00)
■
b3-09: Speed Estimation ACR I Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-09
(0199)
Speed Estimation ACR I
Time
Sets the integral time for the automatic current regulator during Speed Estimation Speed Search. Also
adjusts speed search responsiveness. Usually it is not necessary to change this setting.
Determined by A1-02 when
A1-02 ≠ 5
20.0 when A1-02 = 5
(0.0 - 1000.0 ms)
■
b3-10: Speed Estimation Detection Gain
No.
(Hex.)
Name
Description
Default
(Range)
b3-10
(019A)
Expert
Speed Estimation Detection
Gain
Sets the gain to correct estimated frequencies from Speed Estimation Speed Search.
1.05
(1.00 - 1.20)
If the drive detects
ov [DC Bus Overvoltage]
when you restart the motor, increase the setting value.
Note:
When
A1-02 = 8 [Control Method Selection = EZOLV]
, the default setting is 1.00 and the setting range is 1.00 - 1.10.
■
b3-11: Spd Est Method Switch-over Level
No.
(Hex.)
Name
Description
Default
(Range)
b3-11
(019B)
Expert
Spd Est Method Switch-over
Level
Uses the quantity of voltage in the motor to automatically switch the search method within the type
of speed measurement.
5.0%
(0.5 - 100.0%)
Note:
•
208 V class at 100% = 200 V
•
480 V class at 100% = 400 V
■
b3-12: Speed Search Current Deadband
No.
(Hex.)
Name
Description
Default
(Range)
b3-12
(019C)
Expert
Speed Search Current
Deadband
Sets the minimum current detection level during Speed Search. If the drive does not do Speed
Estimation, increase this setting in 0.1-unit increments.
determined by o2-04
(2.0 - 10.0)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...