Figure 2.73 Acceleration/Deceleration Time Gain through Analog Input
■
6: DC Injection Braking Current
Setting Value
Function
Description
6
DC Injection Braking
Current
Enters a signal to adjust the current level used for DC Injection Braking when the drive rated output current is 100%.
Note:
When you set this function, it will disable the setting value of
b2-02 [DC Injection Braking Current]
.
Figure 2.74 DC Injection Braking Current through Analog Input
■
7: Torque Detection Level
Setting Value
Function
Description
7
Torque Detection Level
Enters a signal to adjust the overtorque/undertorque detection level.
When
A1-02 = 0, 5 [Control Method Selection = V/f, OLV/PM]
, the drive rated current is 100%. When
A1-02 = 8
[EZOLV]
, the motor rated torque is 100%.
Note:
Use this function with
L6-01 [Torque Detection Selection 1]
. This parameter functions as an alternative to
L6-02 [Torque Detection Level 1]
.
■
8: Stall Prevent Level During Run
Setting Value
Function
Description
8
Stall Prevent Level During
Run
Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.
Note:
The Stall Prevent Level During Run is based on the smaller of these two values:
•
Analog input value of MFAI terminal
•
L3-06 [Stall Prevent Level during Run]
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...