TOEPYAIHV6002A HV600 Drive Programming
219
Note:
•
A Loss of Prime condition occurs when the measured quantity set by
Y1-18 [Prime Loss Detection Method]
decreases to this level for the
time set in
Y1-20 [Loss of Prime Time]
and the output frequency is at the
Y4-02 [Pre-Charge Frequency]
level.
•
The drive will respond to the Loss of Prime condition as specified by
Y1-22 [Loss of Prime Selection]
.
•
Display unit and scaling are dependent on System Units.
■
b5-85: Feedback Loss GoTo Freq Timeout
No.
(Hex.)
Name
Description
Default
(Range)
b5-85
(31B3)
RUN
Feedback Loss GoTo Freq
Timeout
When
b5-82 = 3 [Feedback Loss 4
~
20mA Detect Sel = Run At b5-83]
and the Feedback signal is
lost, the drive will run at the
b5-83 [Feedback Loss Goto Frequency]
speed for this length of time,
after which the drive will fault on
FDBKL [WIRE Break]
.
0 s
(0 - 6000 s)
Note:
Set this parameter to 0.0 s to disable the function.
■
b5-86: Feedback Loss Start Delay
No.
(Hex.)
Name
Description
Default
(Range)
b5-86
(31B4)
RUN
Feedback Loss Start Delay
When you initiate an AUTO Run command, the drive will wait for this length of time before it will
fault on
FDBKL [WIRE Break]
or use parameter
b5-83 [Feedback Loss Goto Frequency]
.
0.0 s
(0.0 - 120.0 s)
◆
b8: Energy Saving
Energy-saving control operates the motor at its most efficient level to improve overall system operating efficiency.
When you use V/f Control, set these parameters:
•
b8-01 [Energy Saving Control Selection]
•
b8-04 [Energy Saving Coefficient Value]
•
b8-05 [Power Detection Filter Time]
•
b8-06 [Search Operation Voltage Limit]
Note:
•
Energy-saving control is not appropriate for applications with sudden changes in the load or applications driving heavy loads.
•
Energy-saving control maximizes operation based on precise motor data set to the drive. Do Auto-Tuning and enter the correct information
about the motor before you use Energy-saving control.
■
b8-01: Energy Saving Control Selection
No.
(Hex.)
Name
Description
Default
(Range)
b8-01
(01CC)
Energy Saving Control
Selection
Sets the Energy-saving control function.
0
(0, 1)
0 : Disabled
1 : Enabled
■
b8-04: Energy Saving Coefficient Value
No.
(Hex.)
Name
Description
Default
(Range)
b8-04
(01CF)
Expert
Energy Saving Coefficient
Value
Sets the Energy-saving control coefficient to maintain maximum motor efficiency. The default setting
is for Yaskawa motors.
Determined by E2-11 and
o2-04
(0.00 - 655.00)
When you use a motor from a different manufacturer, increase the setting value in 5% increments to find the
minimum value for
U1-08 [Output Power]
at light loads.
When you decrease the setting value, it decreases the output voltage and decreases power consumption. If the setting
value is too low, the motor will stall.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...