YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
391
Note:
When you set this parameter to 0, the value set in
n1-02 [Hunting Prevention Gain Setting]
is effective when the motor rotates in reverse.
Adjust this parameter in these conditions:
•
When
n1-01 = 1, 2 [Hunting Prevention Selection = Enabled (Normal), Enabled (High Carrier Frequency)]
: If
oscillation occurs when you operate a motor with a light load, increase the setting value in 0.1-unit increments.
•
When
n1-01 = 1, 2
, if the motor stalls: Decrease the setting value in 0.1-unit increments.
■
n1-13: DC Bus Stabilization Control
No.
(Hex.)
Name
Description
Default
(Range)
n1-13
(1B59)
Expert
DC Bus Stabilization
Control
Sets the oscillation suppression function for the DC bus voltage.
0
(0, 1)
0 : Disabled
1 : Enabled
Note:
If the DC bus voltage does not become stable with light loads and the drive detects
ov [Overvoltage]
, set this parameter to 1.
■
n1-14: DC Bus Stabilization Time
No.
(Hex.)
Name
Description
Default
(Range)
n1-14
(1B5A)
Expert
DC Bus Stabilization Time
Adjusts the responsiveness of the oscillation suppression function for the DC bus voltage. Set
n1-13
= 1 [DC Bus Stabilization Control = Enabled]
to enable this parameter.
100.0 ms
(0.0 - 500.0 ms)
Note:
Adjust this parameter in 100 ms increments.
◆
n3: High Slip Braking (HSB) and Overexcitation Braking
n3 parameters
configure High Slip Braking and Overexcitation Deceleration.
■
High Slip Braking
High slip braking quickly decelerates motors without using braking resistors.
This lets you stop a motor more quickly than with the ramp to stop processes. This function is best for applications
that do not frequently stop the motor, for example the fast stop function for high-inertia loads. High Slip Braking
starts when the MFDI for
High Slip Braking (HSB) Activate [H1-xx = 68]
activates.
Figure 2.108 High Slip Braking Time Chart
An induction motor is necessary to use high slip braking. Set
A1-02 = 0 [Control Method Selection = V/f Control]
to
enable high slip braking.
Principles of Operation
HSB significantly decreases the frequency supplied to the motor at the same time that deceleration starts to increase
motor slip.
The drive keeps the motor current at a constant level during deceleration to prevent overvoltage and do automatic
braking and it also keeps a slip level that causes the maximum quantity of deceleration torque.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...