1.4 A: Initialization Parameters
22
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
1.4
A: Initialization Parameters
◆
A1: Initialization
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
A1-00
(0100)
RUN
Language Selection
Sets the language for the HOA keypad.
Note:
When you use
A1-03 [Initialize Parameters]
to initialize the drive, the drive will not
reset this parameter.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
0
(0 - 6)
A1-01
(0101)
RUN
Access Level Selection
Sets user access to parameters. The access level controls which parameters the keypad will
display and which parameters the user can set.
0 : Operation Only
1 : User Parameters
2 : Advanced Level
3 : Expert Level
4 : Lock Parameters
2
(0 - 4)
A1-02
(0102)
Control Method Selection
Sets the control method for the drive application and the motor.
0 : V/f Control
5 : PM Open Loop Vector
8 : EZ Vector Control
0
(0 - 8)
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
3330 : 3-Wire Initialization
3410 : HVAC Initialization
0
(0 - 3410)
A1-04
(0104)
Password
Entry point for the password set in
A1-05 [Password Setting]
. The user can view the
settings of parameters that are locked without entering the password. Enter the correct
password in this parameter to change parameter settings.
0000
(0000 - 9999)
A1-05
(0105)
Password Setting
Sets a password to lock parameters and prevent changes to parameter settings. Enter the
correct password in
A1-04 [Password]
to unlock parameters and accept changes.
0000
(0000 - 9999)
A1-06
(0127)
Application Preset
Sets the drive to operate in selected application conditions.
0 : No Preset Selected
1 : General Purpose Fan
2 : Fan w/ PID Control
3 : Return Fan w/ PID Control
4 : Cooling Tower Fan
5 : Cooling Tower Fan w/ PID
6 : Secondary Pump
7 : Pump w/ PID Control
8 : Pump Network Multiplex
0
(0 - 8)
A1-07
(0128)
DriveWorksEZ Function
Selection
Sets the drive to operate with DriveWorksEZ.
0 : DWEZ Disabled
1 : DWEZ Enabled
2 : Enabled/Disabled wDigital Input
0
(0 - 2)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...