n8-54: Voltage Error Compensation Time
No.
(Hex.)
Name
Description
Default
(Range)
n8-54
(056D)
Expert
Voltage Error Compensation
Time
Sets the time constant that the drive uses when adjusting for voltage errors.
1.00 s
(0.00 - 10.00 s)
Adjust this parameter in these conditions:
•
If oscillation occurs at the time of start up, increase the setting value.
•
If hunting occurs when operating at low speed, increase the setting value.
•
If fast changes in the load cause hunting, increase the setting value in 0.1-unit increments. If you cannot stop
hunting, set
n8-51 [Pull-in Current @ Acceleration]
to 0% and set
n8-54
to 0.00 s, and disable compensation for
voltage errors.
■
n8-55: Motor to Load Inertia Ratio
No.
(Hex.)
Name
Description
Default
(Range)
n8-55
(056E)
Motor to Load Inertia Ratio
Sets the ratio between motor inertia and machine inertia.
0
(0 - 3)
Sets the ratio between motor inertia and machine inertia to adjust the ACR.
Adjust in the following situations.
•
If torque and speed response are unsatisfactory, gradually increase the setting from 0.
•
If the motor does not run smoothly, gradually increase the setting from 0.
•
If the motor stalls during run at constant speed, gradually increase the setting from 0.
•
If there is vibration or hunting, decrease the setting.
Note:
•
If the value too low, the drive will detect
STPo [Motor Step-Out Detected]
.
•
If you use one motor or more than motor at low inertia and the value is too high, there can be vibration in the motor.
0 : Below 1:10
Use this setting in these conditions:
•
The ratio between the motor inertia and machine inertia is less than 1:10
•
There are large current ripples
1 : Between 1:10 and 1:30
Use this setting in these conditions:
•
The ratio between the motor inertia and machine inertia is approximately 1:10 to 1:30
•
Parameter
n8-55 = 0
and the drive detects
STPo
because of an impact load or sudden acceleration/deceleration.
2 : Between 1:30 and 1:50
Use this setting in these conditions:
•
The ratio between the motor inertia and machine inertia is approximately 1:30 to 1:50
•
Parameter
n8-55 = 1
and the drive detects
STPo
because of an impact load or sudden acceleration/deceleration.
3 : Beyond 1:50
Adjust this parameter in these conditions:
•
The ratio between the motor inertia and machine inertia is more than 1:50
•
Parameter
n8-55 = 2
and the drive detects
STPo
because of an impact load or sudden acceleration/deceleration.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...