Note:
Make sure that you also set jumper S5 on the control circuit terminal block when you change this parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
■
H4-08: Terminal AM Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-08
(0424)
Terminal AM Signal Level
Select
Sets the MFAO terminal AM output signal level.
0
(0, 2)
Note:
Make sure that you also set jumper S5 on the control circuit terminal block when you change this parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
■
H4-20: Analog Power Monitor 100% Level
No.
(Hex.)
Name
Description
Default
(Range)
H4-20
(0B53)
Analog Power Monitor
100% Level
Sets the level at 10 V when you set
U1-08 [Output Power]
for analog output.
0.00 kW
(0.00 - 650.00 kW)
Note:
•
When
H4-20 = 0.00 kW
, the output power monitor 10 V level = motor rated power. The setting changes when the
A1-02 [Control Method
Selection]
value changes:
–
A1-02 = 0 [V/f]
:
E2-11 [Motor Rated Power]
–
A1-02 = 5 [OLV/PM]
:
E5-02 [PM Motor Rated Power]
–
A1-02 = 8 [EZOLV]
:
E9-07 [Motor Rated Power]
◆
H5: Memobus/Modbus Communication
H5 parameters
configure the drive to use MEMOBUS/Modbus communications.
You can use the MEMOBUS/Modbus protocol over the RS-485 port (terminals D+ and D-) in the drive to use serial
communication with programmable controllers (PLC).
■
H5-01: Drive Node Address
No.
(Hex.)
Name
Description
Default
(Range)
H5-01
(0425)
Drive Node Address
Sets the communication slave address for drives.
1FH
(0 - FFH)
Note:
•
Restart the drive after you change the parameter setting.
•
Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
•
When
Y1-01 = 3 [Multiplex Mode = Memobus Network]
, the setting range changes when the
Y9-25 [Highest Node Address]
setting
changes.
To enable the drive to communicate with the controller (master) over MEMOBUS/Modbus communications, you
must set the drive with a slave address. Set
H5-01 ≠ 0
.
Set a slave address that is different from other slave devices.
■
H5-02: Communication Speed Selection
No.
(Hex.)
Name
Description
Default
(Range)
H5-02
(0426)
Communication Speed
Selection
Sets the communications speed for MEMOBUS/Modbus communications.
3
(0 - 8)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...