YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
115
No.
(Hex.)
Name
Description
MFAO Signal Level
U1-61
(108A)
System Feedback
Shows the PID Feedback.
Unit: 0.01%
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-
39 [PID User Unit Display Digits]
set the unit, range, and resolution.
No signal output available
U1-64
(108D)
Motor Speed
Shows the absolute value of the parameter
U1-02 [Output Frequency]
converted to RPM.
Unit: 1 RPM
No signal output available
U1-99
(3BAE)
Anti-No-Flow Timer
Shows the value of the anti-no-flow timer. When this value is at the
Y2-24 [Anti-No-Flow Detection
Time]
setting, the anti-no-flow feature starts to decrease the output frequency.
Unit: 0.1 s
No signal output available
◆
U2: Fault Trace
No.
(Hex.)
Name
Description
MFAO Signal Level
U2-01
(0080)
Current Fault
Shows the fault that the drive has when viewing the monitor.
No signal output available
U2-02
(0081)
Previous Fault
Shows the fault that occurred most recently.
No signal output available
U2-03
(0082)
Freq Reference@Fault
Shows the frequency reference at the fault that occurred most recently.
Use
U1-01 [Frequency Reference]
to monitor the frequency reference value.
Unit: 0.01 Hz
No signal output available
U2-04
(0083)
Output Freq @ Fault
Shows the output frequency at the fault that occurred most recently.
Use
U1-02 [Output Frequency]
to monitor the actual output frequency.
Unit: 0.01 Hz
No signal output available
U2-05
(0084)
Output Current@Fault
Shows the output current at the fault that occurred most recently.
Use
U1-03 [Output Current]
to monitor the output current. The keypad shows the value of
U1-03
in
amperes (A).
When you use serial communications to show the monitor, the current is
“
8192 = drive rated current
(A)
”
. Use the formula:
“
Numerals being displayed / 8192 × drive rated current (A)
”
to use the serial
communication current value shown in the monitor.
Unit: Determined by the drive model.
•
0.01 A: 2011 to 2046, 4005 to 4014
•
0.1 A: 2059 to 2273, 4021 to 4302
No signal output available
U2-06
(0085)
Motor Speed @ Fault
Shows the motor speed at the fault that occurred most recently.
Use
U1-05 [Motor Speed]
to monitor the motor speed.
Unit: 0.01 Hz
No signal output available
U2-07
(0086)
Output Voltage@Fault
Shows the output voltage reference at the fault that occurred most recently.
Use
U1-06 [Output Voltage Ref]
to monitor the output voltage reference.
Unit: 0.1 V
No signal output available
U2-08
(0087)
DC Bus Voltage@Fault
Shows the DC bus voltage at the fault that occurred most recently.
Use
U1-07 [DC Bus Voltage]
to monitor the DC bus voltage.
Unit: 1 V
No signal output available
U2-09
(0088)
Output Power @ Fault
Shows the output power at the fault that occurred most recently.
Use
U1-08 [Output Power]
to monitor the output power.
Unit: 0.1 kW
No signal output available
U2-10
(0089)
Torque Ref @ Fault
Shows the torque reference at the fault that occurred most recently as a percentage of the motor rated
torque.
Use
U1-09 [Torque Reference]
to monitor the torque reference.
Unit: 0.1%
No signal output available
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...