YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
121
No.
(Hex.)
Name
Description
MFAO Signal Level
U4-09
(005E)
LED Check
Turns on the LED Status Ring and all of the keypad LEDs to make sure that the LEDs operate
correctly.
1.
Set
o2-24 = 0 [LED Light Function Selection = Enable Status Ring & Keypad LED]
.
2.
Push
with
U4-09
shown on the keypad.
All LEDs on the keypad and LED Status Ring will turn on.
Note:
When Safety input 2 CH is open (STo), READY will flash.
No signal output available
U4-10
(005C)
kWh, Lower 4 Digits
Shows the lower 4 digits of the watt hour value for the drive.
Unit: 1 kWh
Note:
The watt hour is displayed in 9 digits. Monitor
U4-11 [kWh, Upper 5 Digits]
shows the upper 5
digits and
U4-10
shows the lower 4 digits.
Example for 12345678.9 kWh:
U4-10
:
678.9 kWh
U4-11
:
12345 MWh
No signal output available
U4-11
(005D)
kWh, Upper 5 Digits
Shows the upper 5 digits of the watt hour value for the drive.
Unit: 1 MWh
Note:
Monitor
U4-11
shows the upper 5 digits and
U4-10 [kWh, Lower 4 Digits]
shows the lower 4
digits.
Example for 12345678.9 kWh:
U4-10
: 678.9 kWh
U4-11
: 12345 MWh
No signal output available
U4-13
(07CF)
Peak Hold Current
Shows the hold value of the peak value (rms) for the drive output current.
Use
U4-14 [PeakHold Output Freq]
to show the drive output frequency at the time that the drive
holds the output current.
The drive will hold the peak hold current at the next start up and restart of the power supply.
The drive keeps the held value during baseblock (during stop).
The keypad shows the value of
U4-13
in amperes (A). When you use serial communications to show
the monitor, the current is
“
8192 = drive rated current (A).
”
Use the formula:
“
Numerals being
displayed / 8192 × drive rated current (A)
”
to use the serial communication current value shown in
the monitor.
Unit: Determined by the drive model.
•
0.01 A: 2011 to 2046, 4005 to 4014
•
0.1 A: 2059 to 2273, 4021 to 4302
No signal output available
U4-14
(07D0)
PeakHold Output Freq
Shows the output frequency at which the peak value (rms) of the drive output current is held.
The peak hold current can be monitored by
U4-13 [Peak Hold Current]
.
The peak hold output frequency will be cleared at the next startup and restart of the power supply.
The drive keeps the value that was under hold during baseblock (during stop).
Unit: 0.01 Hz
No signal output available
U4-16
(07D8)
Motor oL1 Level
Shows the integrated value of
oL1 [Motor Overload]
as a percentage of
oL1
detection level.
Unit: 0.1%
10 V: 100%
U4-18
(07DA)
Reference Source
Shows the selected frequency reference source.
The keypad shows the frequency reference source as
“
XY-nn
”
as specified by these rules:
X: Frequency reference
•
1:
b1-01 [Frequency Reference Selection 1]
Y-nn: Frequency reference source
•
0-01: Keypad (
d1-01 [Reference 1]
)
•
1-00: Analog input (unassigned)
•
1-01: MFAI terminal A1
•
1-02: MFAI terminal A2
•
2-02 to 2-17: Multi-step speed reference (
d1-02 to d1-17 [Reference 2 to 8, Jog Reference]
)
•
3-01: Serial communications
•
4-01: Communication option card
•
7-01: DriveWorksEZ
•
9-01: Up/Down command
•
B-00: Hand Reference 1 (Analog)
•
B-01: Hand Reference 1 (
S5-05 [HAND Frequency Reference]
)
No signal output available
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...