365
Note:
•
This parameter is applicable when
L3-05 = 1, 2 [Stall Prevention during RUN = Deceleration Time 1 (C1-02), Deceleration Time 2 (C1-
04)]
.
•
When
L3-23 = 1 [Stall P Reduction at Constant HP = Automatic Reduction @ CHP Region]
, the drive will automatically decrease the level
in the constant output range.
Use an Analog Input to Change the Stall Prevent Level during Run
When
H3-xx = 8 [MFAI Function Selection = Stall Prevent Level During Run]
, you can change the stall prevention
level during run through the input gain and bias settings for terminals A1 and A2.
If you set the input level for terminals A1 and A2 and
L3-06
, the drive will use the smaller value for Stall Prevent
Level during Run.
Figure 2.92 Stall Prevention Level during Run with Analog Input
■
L3-11: Overvoltage Suppression Select
No.
(Hex.)
Name
Description
Default
(Range)
L3-11
(04C7)
Overvoltage Suppression
Select
Sets the overvoltage suppression function.
0
(0, 1)
0 : Disabled
The drive does not adjust the regenerative torque limit or the output frequency. If you apply a regenerative load, the
drive can detect an
ov [Overvoltage]
fault.
1 : Enabled
When a regenerative load increases the DC bus voltage, the drive decreases the regenerative torque limit and
increases the output frequency to prevent
ov
.
■
L3-17: DC Bus Regulation Level
No.
(Hex.)
Name
Description
Default
(Range)
L3-17
(0462)
DC Bus Regulation Level
Sets the target value for the DC bus voltage when the overvoltage suppression function and the Decel
Stall Prevention function (Intelligent Stall Prevention) are active.
208 V Class: 375 V,
480 V Class: 750 V
(208 V Class: 150 - 400 V,
480 V Class: 300 - 800 V)
Note:
This value is initialized when
E1-01 [Input AC Supply Voltage]
is changed.
Sets this parameter for any of the following circumstances.
•
L3-11 = 1 [OV Suppression Function Select = Enabled]
.
•
L3-04 = 2 [Decel Stall Prevention Selection = Automatic Decel Reduction]
.
■
L3-20: DC Bus Voltage Adjustment Gain
No.
(Hex.)
Name
Description
Default
(Range)
L3-20
(0465)
Expert
DC Bus Voltage Adjustment
Gain
Sets the proportional gain used to control the DC bus voltage.
Determined by A1-02
(0.00 - 5.00)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...