YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
451
■
S5-10: AUTO Key Memory at Power Down
No.
(Hex.)
Name
Description
Default
(Range)
S5-10
(3280)
RUN
AUTO Key Memory at
Power Down
Sets the function to keep the AUTO Mode status when you de-energize the drive.
2
(0 - 2)
0 : Disabled
The drive always powers up in OFF Mode.
1 : Enabled w/ Memory
When you de-energize the drive, the drive saves the AUTO Mode status. When you energize the drive again, the drive
goes straight to AUTO Mode when you use the keypad to input the AUTO command.
2 : AUTO Mode
The drive always powers up in AUTO Mode.
◆
S6: Protection
S6 parameters
set the Emergency Override function.
■
Emergency Override
The Emergency Override function ignores faults and alarms that can stop the drive and will force the drive to run with
a set speed or the frequency reference. You can use this function for an applications where it is necessary to continue
the drive operation when there is an emergency situation with the installation, for example, smoke purge.
Emergency Override function will be active when:
•
The terminal set for
H1-xx = AF or B0 [MFDI Function Selection = Emergency Override FWD or REV]
is active
•
You set bit 1 in MEMOBUS Register 15FBH for Emergency Override FWD or bit 2 in MEMOBUS register for
Emergency Override REV
If FWD and REV Emergency Override selections are active at the same time, an
EF [External Fault]
will occur.
The values set in
S6-09 [Emergency Override Min Speed]
and
S6-10 [Emergency Override Max Speed]
are the lower
limit and upper limit for the output frequency during Emergency Override. The drive applies upper and lower limit
values to
S6-02 [Emergency Override Ref Selection]
.
While the drive is in Emergency Override Mode, the drive records the operation time in
U4-61 [Total EMOVR Run
Time]
. When the value is more than 60000 min, the alternation timer is at its maximum value. When you set
A1-03 =
2220 or 3300 [Initialize Parameters = 2-Wire Initialization or 3-Wire Initialization]
to initialize the drive, the drive
will not reset the counter.
Functions Ignored by Emergency Override
When the drive is in factory default setting, Emergency Override ignores these digital inputs:
•
Drive Enable
•
Drive Enable 2
•
Customer Safeties
•
BAS Interlock
The drive will give priority to these inputs over Emergency Override when you set
S6-08 [EMOVR Drive Enable
Input Mode]
,
S6-16 [EMOVR Customer Safety Mode]
, or
S6-17 [EMOVR BAS Interlock Mode]
correctly.
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...