S2-10
(320F)
Timer 2 Reference Source
Selects the frequency reference source to run the drive when sequence timer 2 is active
(only applicable when
S2-09 > 0 [Timer 2 Sequence Selection ≠ 0]
).
0 : Operator (d1-01/YA-01)
1 : Operator (d1-02/YA-02)
2 : Operator (d1-03/YA-03)
3 : Operator (d1-04/YA-04)
4 : Terminals
5 : Serial Com
6 : Option PCB
8 : Set by b1-01
Note:
For reference source 0 to 3, the drive will use
d1-xx
frequency reference when PID
mode is disabled and
YA-xx
setpoint when PID is enabled.
0
(0 - 8)
S2-11
(3210)
Timer 3 Start Time
Sets the start time for timer 3.
Note:
•
Default is when
o4-22 = 1 [Time Format = 12 Hour Clock]
. When
o4-22 = 0 [24
Hour Clock]
, default is 00:00. When
o4-22 = 2 [12 Hour JP Clock]
, default is 00:00
AM.
•
Range is when
o4-22 = 1
. When
o4-22 = 0
, range is 00:00 to 24:00. When
o4-22 =
2
, range is 00:00 AM to 11:59 PM.
12:00
(12:00 AM - 11:59 PM)
S2-12
(3211)
Timer 3 Stop Time
Sets the stop time for timer 3.
Note:
•
Default is when
o4-22 = 1 [Time Format = 12 Hour Clock]
. When
o4-22 = 0 [24
Hour Clock]
, default is 00:00. When
o4-22 = 2 [12 Hour JP Clock]
, default is 00:00
AM.
•
Range is when
o4-22 = 1
. When
o4-22 = 0
, range is 00:00 to 24:00. When
o4-22 =
2
, range is 00:00 AM to 11:59 PM.
12:00
(12:00 AM - 11:59 PM)
S2-13
(3212)
Timer 3 Day Selection
Sets the days for which sequence timer 3 is active.
0 : Timer Disabled
1 : Daily
2 : Mon - Fri
3 : Sat - Sun
4 : Monday
5 : Tuesday
6 : Wednesday
7 : Thursday
8 : Friday
9 : Saturday
10 : Sunday
0
(0 - 10)
S2-14
(3213)
Timer 3 Sequence
Selection
Sets the drive response when sequence timer 3 is active.
0 : Digital Out Only
1 : Run
2 : Run - PID Disable
3 : Allow Alternation
0
(0 - 3)
S2-15
(3214)
Timer 3 Reference Source
Selects the frequency reference source to run the drive when sequence timer 3 is active
(only applicable when
S2-14 > 0 [Timer 3 Sequence Selection ≠ Digital Out Only]
).
0 : Operator (d1-01/YA-01)
1 : Operator (d1-02/YA-02)
2 : Operator (d1-03/YA-03)
3 : Operator (d1-04/YA-04)
4 : Terminals
5 : Serial Com
6 : Option PCB
8 : Set by b1-01
Note:
For reference source 0 to 3, the drive will use
d1-xx
frequency reference when PID
mode is disabled and
YA-xx
setpoint when PID is enabled.
0
(0 - 8)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...