YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
311
OFF : The output frequency < “
L4-01
-
L4-02
”, or the output frequency
≤
L4-01
L4-01:
L4-02:
Figure 2.64 Frequency Detection 2 Time Chart
■
6: Drive Ready
Setting Value
Function
Description
6
Drive Ready
The terminal activates when the drive is ready and running.
The terminal deactivates in these conditions:
•
When the power supply is OFF
•
During a fault
•
When there is problem with the control power supply
•
When there is a parameter setting error and the drive cannot operate although there is a Run command
•
When you enter a Run command and it immediately triggers an overvoltage or undervoltage fault because the drive
has an overvoltage or undervoltage fault during stop
•
When the drive is in Programming Mode and will not accept a Run command
•
When the Safe Disable function is active
■
7: DC Bus Undervoltage
Setting Value
Function
Description
7
DC Bus Undervoltage
The terminal activates when the DC bus voltage or control circuit power supply is at the voltage set in
L2-05 [Undervoltage
Detection Lvl (Uv1)]
or less. The terminal also activates when there is a fault with the DC bus voltage.
ON : The DC bus voltage
≤
L2-05
OFF : The DC bus voltage >
L2-05
■
8: During Baseblock (N.O.)
Setting Value
Function
Description
8
During Baseblock (N.O.)
The terminal activates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
ON : During baseblock
OFF : The drive is not in baseblock.
■
9: Frequency Reference from Keypad
Setting Value
Function
Description
9
Frequency Reference from
Keypad
Shows the selected frequency reference source.
ON : The keypad is the frequency reference source.
OFF : Parameter
b1-01 [Frequency Reference Selection 1]
is the frequency reference source.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...