YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
313
■
13: Speed Agree 2
Setting Value
Function
Description
13
Speed Agree 2
The terminal activates when the output frequency is in the range of the frequency reference ±
L4-04 [Speed Agree Detection Width
(+/-)]
.
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of “frequency reference
±
L4-04
”.
OFF : The output frequency is not in the range of “frequency reference
±
L4-04
”.
L4-04:
Figure 2.65 Speed Agree 2 Time Chart
■
14: User-Set Speed Agree 2
Setting Value
Function
Description
14
User-Set Speed Agree 2
The terminal activates when the output frequency is in the range of
L4-03 [Speed Agree Detection Level (+/-)]
±
L4-04 [Speed
Agree Detection Width (+/-)]
and in the range of the frequency reference ±
L4-04
.
Note:
The detection level set in
L4-03
is a signed value. The drive will only detect in one direction.
ON : The output frequency is in the range of “
L4-03
±
L4-04
” and the range of frequency reference
±
L4-04
.
OFF : The output frequency is not in the range of “
L4-03
±
L4-04
” or the range of frequency
reference
±
L4-04
.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...