TOEPYAIHV6002A HV600 Drive Programming
Table 4.7 Power Supply and Alarm Display
Main Circuit Power Supply
External 24 V Power Supply
o2-23
[External 24V Powerloss
Detection]
o2-26
[Alarm Display at Ext. 24V
Power]
Alarm Display
ON
ON
-
-
-
ON
OFF
0 [Disabled]
-
-
1 [Enabled]
-
L24v [Loss of External Power 24
Supply]
OFF
ON
-
0 [Disabled]
“
Ready
”
LED light flashes quickly
-
1 [Enabled]
EP24v [External Power 24V
Supply]
■
Serial Communication Terminals
Refer to
for a list of serial communication terminals and functions.
Table 4.8 Serial Communication Terminals
Type
Terminal
Terminal Name
Function (Signal Level)
Serial Communication
D+
Communication
input/output (+)
•
APOGEE FLN communications
•
BACnet communications
•
MEMOBUS/ Modbus communications
•
Metasys N2 communications
Use an RS-485 cable to connect the drive.
Note:
Set DIP switch S2 to ON to enable the
termination resistor in the last drive in an
APOGEE FLN, BACnet, MEMOBUS/ Modbus,
or Metasys N2 network.
•
RS-485
•
APOGEE FLN communications: 4.8 kbps
•
BACnet communications: Maximum 76.8 kbps
•
MEMOBUS/Modbus communications:
Maximum 115.2 kbps
•
Metasys N2 communications: 9.6 kbps
D-
Communication
output (-)
AC
Signal ground
0 V
FE
Option card ground
-
◆
Control Circuit Terminal Configuration
The control circuit terminals are in the positions shown in
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...