TOEPYAIHV6002A HV600 Drive Programming
■
84: Dedicated Multi-Setpoint YA-03
Setting Value
Function
Description
84
Dedicated Multi-Setpoint
YA-03
Sets the function to set the PID setpoint to
YA-03 [Setpoint 3]
. Set this function and
H1-xx = 83 [Dedicated Multi-Setpoint YA-02]
at
the same time.
Note:
If you use this function and one of
H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2]
at the same time, the drive will detect an
oPE03 [Multi-
Function Input Setting Err]
.
ON :
YA-03
is PID setpoint.
OFF :
YA-01 [Setpoint 1]
,
YA-02 [Setpoint 2]
, or
YA-04 [Setpoint 4]
is PID setpoint.
■
85: Dedicated Multi-Setpoint YA-04
Setting Value
Function
Description
85
Dedicated Multi-Setpoint
YA-04
Sets the function to set the PID setpoint to
YA-04 [Setpoint 4]
. Set this function,
H1-xx = 83 [Dedicated Multi-Setpoint YA-02]
, and
H1-xx = 84 [Dedicated Multi-Setpoint YA-03]
at the same time.
Note:
If you use this function and one of
H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2]
at the same time, the drive will detect an
oPE03 [Multi-
Function Input Setting Err]
.
ON :
YA-04
is PID setpoint.
OFF :
YA-01 [Setpoint 1]
,
YA-02 [Setpoint 2]
, or
YA-03 [Setpoint 3]
is PID setpoint.
■
88: Thermostat Fault
Setting Value
Function
Description
88
Thermostat Fault
Sets the drive to show the
VLTS [Thermostat Fault]
when the input terminal is ON.
Note:
This function is active when the drive is running.
If the drive is running in AUTO Mode or HAND Mode and if the terminal set for
H1-xx = 88 [MFDI Function
Selection = Thermostat Fault]
is ON or if the terminal set for
H1-xx = 188 [!Thermostat Fault]
is OFF, the drive will
detect
VLTS
.
■
90 to 96: DriveWorksEZ Digital Inputs 1 to 7
Setting Value
Function
Description
90 - 96
DWEZ Digital Inputs 1 to 7
Set DriveWorksEZ digital inputs. Refer to the DriveWorksEZ online manual for more information.
Note:
You cannot set values 90 to 96 for inverse output.
■
9F: DWEZ Disable
Setting Value
Function
Description
9F
DWEZ Disable
Sets operation of the DriveWorksEZ program saved in the drive.
Note:
Set
A1-07 = 2 [DriveWorksEZ Function Selection = Digital input]
to use this function.
ON : Disabled
OFF : Enabled
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...