E3-13: Motor 2 Base Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E3-13
(0347)
Expert
Motor 2 Base Voltage
Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern for the
constant output range. Usually it is not necessary to change this parameter.
0.0 V
(208 V Class: 0.0 - 255.0 V,
480 V Class: 0.0 - 510.0 V)
Note:
•
When you initialize the drive, this parameter is reset to the default value.
•
The setting value changes automatically when you do Auto-Tuning (rotational and stationary 1 or 2).
◆
E4: Motor 2 Parameters
E4 parameters [Motor 2 Parameters]
set induction motor data. To switch drive operation from one motor to a
different motor, configure motor 2.
Auto-Tuning automatically sets the
E4 parameters
to the best values for the application. If you cannot do Auto-
Tuning, set the
E4 parameters
manually.
Note:
E3-xx
and
E4-xx
are available when
H1-xx = 16 [MFDI Function Select = Motor 2 Selection]
.
■
E4-01: Motor 2 Rated Current
No.
(Hex.)
Name
Description
Default
(Range)
E4-01
(0321)
Motor 2 Rated Current
Sets the motor rated current for motor 2 in amps.
Determined by o2-04
(10% to 200% of the drive
rated current)
Note:
•
If
E4-01 ≤ E4-03 [Motor 2 Rated No-Load Current]
, the drive will detect
oPE02 [Parameter Range Setting Error]
.
•
The default settings and setting ranges are in these units:
–
0.01 A: 2011 to 2046, 4005 to 4014
–
0.1 A: 2059 to 2273, 4021 to 4302
The value set for
E4-01
becomes the reference value for motor protection and the torque limit. Enter the motor rated
current written on the motor nameplate. Auto-Tuning automatically sets the value of
E4-01
to the value input for
[Motor Rated Current].
■
E4-02: Motor 2 Rated Slip
No.
(Hex.)
Name
Description
Default
(Range)
E4-02
(0322)
Motor 2 Rated Slip
Sets the motor rated slip for motor 2.
Determined by o2-04
(0.000 - 20.000 Hz)
The value set in
E4-02
becomes the base slip compensation value. The drive sets this parameter during Rotational
Auto-Tuning and Stationary Auto-Tuning. If you cannot do Auto-Tuning, use the information written on the motor
nameplate and this formula to calculate the motor rated slip:
E4-02
= f - (n × p) / 120
•
f: Motor rated frequency (Hz)
•
n: Rated motor speed (min
-1
(r/min))
•
p: Number of motor poles
■
E4-03: Motor 2 Rated No-Load Current
No.
(Hex.)
Name
Description
Default
(Range)
E4-03
(0323)
Motor 2 Rated No-Load
Current
Sets the no-load current for motor 2 in amps when operating at the rated frequency and the no-load
voltage.
Determined by o2-04
(Less than 0 - E4-01)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...