Note:
When you set this parameter, also set
E5-24 = 0.0
. The drive will detect
oPE08 [Parameter Selection Error]
in these conditions:
•
E5-09 = 0.0
and
E5-24 = 0.0
•
E5-09 ≠ 0.0
and
E5-24 ≠ 0.0
■
E5-24: PM Back-EMF L-L Vrms (mV/rpm)
No.
(Hex.)
Name
Description
Default
(Range)
E5-24
(0353)
PM Back-EMF L-L Vrms
(mV/rpm)
Sets the RMS value for PM motor line voltage.
0.1 mV/min
-1
(0.0 - 6500.0 mV/min
-1
)
Set this parameter when you use an SPM motor.
PM motor Auto-Tuning automatically sets this parameter to the value of [Back-EMF Voltage Constant (Ke)].
When
E5-01 = FFFF
, only set
E5-09 [PM Back-EMF Vpeak (mV/(rad/s))]
or
E5-24
as the induced voltage constant.
Note:
When you set this parameter, also set
E5-09 = 0.0
. The drive will detect
oPE08 [Parameter Selection Error]
in these conditions:
•
E5-09 = 0.0
and
E5-24 = 0.0
•
E5-09 ≠ 0.0
and
E5-24 ≠ 0.0
◆
E9: Motor Setting
E9 parameters
set SynRM motors. Set these parameters to derate torque applications when a high level of
responsiveness and accurate speed control are not necessary. Auto-Tuning the drive will automatically set the
E9
parameters
.
If you cannot do EZ Tuning, you can also manually set the
E9 parameters
.
■
E9-01: Motor Type Selection
No.
(Hex.)
Name
Description
Default
(Range)
E9-01
(11E4)
Motor Type Selection
Sets the type of motor.
0
(0 to 2)
EZ Tuning automatically sets this parameter to the value of [Motor Type Selection].
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
■
E9-02: Maximum Speed
No.
(Hex.)
Name
Description
Default
(Range)
E9-02
(11E5)
Maximum Speed
Sets the maximum speed of the motor.
Determined by E9-01
(40.0 - 120.0 Hz)
EZ Tuning automatically sets this parameter to the value of [Motor Max Revolutions].
■
E9-03: Rated Speed
No.
(Hex.)
Name
Description
Default
(Range)
E9-03
(11E6)
Rated Speed
Sets the rated rotation speed of the motor.
Determined by E9-01
(100 - 7200 min
-1
)
EZ Tuning automatically sets this parameter to the value of [Rated Speed].
Note:
Set
E9-01 = 0 [Motor Type Selection = Induction (IM)]
before you set this parameter.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...