TOEPYAIHV6002A HV600 Drive Programming
263
Note:
Set
E9-01 = 0 [Motor Type Selection = Induction (IM)]
before you set this parameter.
■
E9-10: Motor Line-to-Line Resistance
No.
(Hex.)
Name
Description
Default
(Range)
E9-10
(11ED)
Motor Line-to-Line
Resistance
Sets the line-to-line resistance for the motor stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
Note:
This value is the motor line-to-line resistance. Do not set this parameter with the per-phase resistance.
Stationary Auto-Tuning automatically sets this parameter. If you cannot do Stationary Auto-Tuning, use the test report
from the motor manufacturer. You can calculate the motor line-to-line resistance with one of these formulas:
•
E-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
•
B-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
•
F-type insulation: the resistance value (Ω) shown on the test report at 115 °C × 0.87
V/f
OLV/PM
OLV/PM
EZOLV