A: Accel/Decel Ramp Hold
Setting Value
Function
Description
A
Accel/Decel Ramp Hold
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency that was
stored in the drive at the time of the pause, and restarts motor operation.
If the terminal is deactivated, the drive restarts acceleration and deceleration.
When the acceleration/deceleration ramp hold terminal is activated and
d4-01 = 1 [Freq Reference Retention Select =
Enabled]
, the drive will store the output frequency in memory. While the acceleration/deceleration ramp hold
command is activated, the drive will always restart the motor at this output frequency.
Note:
Refer to
d4-01: Freq Reference Hold Selection on page 242
for more information.
■
B: Overheat Alarm (oH2)
Setting Value
Function
Description
B
Overheat Alarm (oH2)
Sets the drive to display an
oH2 [Drive Overheat Warning]
alarm when the input terminal is ON. The alarm does not have an effect
on drive operation.
■
C: Analog Terminal Enable Selection
Setting Value
Function
Description
C
Analog Terminal Enable
Selection
Sets the command that enables or disables the terminals selected in
H3-14 [Analog Input Terminal Enable Sel]
.
ON : Terminal selected with
H3-14
is enabled
OFF : Terminal selected with
H3-14
is disabled
■
E: ASR Integral Reset
Setting Value
Function
Description
E
ASR Integral Reset
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
ON : P control
OFF : PI control
■
F: Not Used
Setting Value
Function
Description
F
Not Used
Use this setting for unused terminals or to use terminals in through mode.
Through Mode uses the signal input to the terminal as a digital input for the upper sequence through a communication
option or MEMOBUS/Modbus communications. This input signal does not have an effect on drive operation.
■
10: Up Command
Setting Value
Function
Description
10
Up Command
Sets the command to use a push button switch to increase the drive frequency reference. You must also set
Setting 11 [Down
Command]
.
ON : Increases the frequency reference.
OFF : Holds the current frequency reference.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...