Note:
•
To use the N.C. switch to input the fast stop command, set 17 (Fast Stop (N.C.)).
•
Refer to
C1-09: Fast Stop Time on page 224
for more information.
•
Set
C1-09 [Fast Stop Time]
to a correct deceleration time. If the deceleration time is too short, it can cause an overvoltage fault and failure
to stop the motor from coasting.
■
16: Motor 2 Selection
Setting Value
Function
Description
16
Motor 2 Selection
Sets the command for the drive to operate motor 1 or motor 2. Stop the motors before switching.
You can use an external input to switch operation between two induction motors. The drive will save the control
methods, V/f patterns, and motor parameters for the two motors.
ON : Selects motor 2.
OFF : Selects motor 1.
When you select motor 2, the drive will switch to motor 2 parameters.
Table 2.49 Parameters that Switch between Motor 1 and Motor 2
Parameter
Motor 2 Selection
OFF (Motor 1)
ON (Motor 2)
C1-xx [Accel & Decel Time]
C1-01 to C1-04
C1-05 to C1-08
C3-xx [Slip Compensation]
C3-01, C3-02
C3-21 to C3-24
C4-xx [Torque Compensation]
C4-01
C4-07
C5-xx [Automatic Speed Regulator (ASR)]
C5-01 to C5-08
C5-01 to C5-08
E1-xx, E3-xx [V/f Patterns]
E2-xx, E4-xx [Motor Parameters]
E1-xx, E2-xx
E3-xx, E4-xx
Note:
•
When you use 2 motors, the drive applies the protective function set in
L1-01 [Motor Overload (oL1) Protection]
to motor 1 and motor 2.
•
You cannot switch between motors 1 and 2 during run. If you try to switch motors when they are running, it will cause a
rUn [Motor Switch
during Run]
alarm.
•
You must wait 200 ms minimum to input a Run command.
•
If you set
H1-xx = 16 [Motor 2 Selection]
and set different control methods in maximum output frequency to motors 1 and 2, the drive will
apply the lower of the two maximum to the two motors. The upper limit of
d1-xx [Frequency Reference]
will change. For example, the
upper limit of
d1-xx
will be 400 when you set these parameters to these values:
–
A1-02 = 5 [Control Method Selection = OLV/PM]
–
E1-04 = 590 [Maximum Output Frequency = 590 Hz]
–
E3-01 = 0 [Motor 2 Control Mode Selection = V/f Control]
–
E3-04 = 400 [Motor 2 Maximum Output Frequency = 400 Hz]
•
For software version PRG: 01011, when Motor 2 Selection is ON, the drive sets acceleration and deceleration times to 10.0 s.
■
17: Fast Stop (N.C.)
Setting Value
Function
Description
17
Fast Stop (N.C.)
Sets the command to ramp to stop in the deceleration time set in
C1-09 [Fast Stop Time]
when the input terminal is activated while
the drive is operating.
If you cancel the fast stop input, the drive will not restart the motor until you meet these conditions:
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...