30: DWEZ Analog Input 1
Setting Value
Function
Description
30
DWEZ Analog Input 1
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
■
31: DWEZ Analog Input 2
Setting Value
Function
Description
31
DWEZ Analog Input 2
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
◆
H4: Analog Outputs
H4 parameters
set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias, and
select output signal levels.
■
Calibrate Meters Connected to MFAO Terminals FM and AM
To calibrate the meters connected to terminals FM and AM, use these parameters:
•
H4-02 [Terminal FM Analog Output Gain]
•
H4-03 [Terminal FM Analog Output Bias]
•
H4-05 [Terminal AM Analog Output Gain]
•
H4-06 [Terminal AM Analog Output Bias]
Set these parameters where the output voltage of 10 V and output current of 20 mA are 100% of the signal level. Use
jumper switch S5 and
H4-07 [Terminal FM Signal Level Select]
or
H4-08 [Terminal AM Signal Level Select]
to select
the voltage output and current output.
No.
Name
Range
Default
H4-02
Terminal FM Analog Output Gain
-999.9 - +999.9%
100.0%
H4-03
Terminal FM Analog Output Bias
-999.9 - +999.9%
0.0%
H4-05
Terminal AM Analog Output Gain
-999.9 - +999.9%
50.0%
H4-06
Terminal AM Analog Output Bias
-999.9 - +999.9%
0.0%
H4-07
Terminal FM Signal Level Select
0: 0 to 10 Vdc
2: 4 to 20 mA
0
H4-08
Terminal AM Signal Level Select
0: 0 to 10 Vdc
2: 4 to 20 mA
0
and
show the gain and bias when
H4-07 = 0 [0 to 10 Vdc]
and
H4-08 = 0 [0 to 10 Vdc]
.
Figure 2.78 Analog Output Gain/Bias Configuration Example 1
For example, when the parameter value set to analog output is 0, and a 3 V signal is output to terminal FM,
H4-03
[Terminal FM Analog Output Bias]
is set to 30%.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...